GE P4A Technical Manual page 826

Micom p40 agile single br eaker multi-end current differential ied (non distance)
Table of Contents

Advertisement

Appendix B - Settings and Signals
ORDINAL
DDB mapped in PSL from opto input (Bus VT secondary MCB tripped or VT fail detected by external VTS scheme), or signal from host relay VTS
scheme
1522
Inhibit LL
DDB mapped in PSL from opto input (external signal to inhibit Live Line function)
1523
Inhibit DL
DDB mapped in PSL from opto input (external signal to inhibit Dead Line function)
1524
Inhibit LB
DDB mapped in PSL from opto input (external signal to inhibit Live Bus function)
1525
Inhibit DB
DDB mapped in PSL from opto input (external signal to inhibit Dead Bus function)
1526
CB In Service
CB In Service (can be initiated for autoreclose)
1528
CB NoAR
CB not available for autoreclose
1535
Trip AR MemA
A Ph trip & AR initiation memory
1536
Trip AR MemB
B Ph trip & AR initiation memory
1537
Trip AR MemC
C Ph trip & AR initiation memory
1541
AR Start
Any AR initiation signal present
1542
ARIP
Any AR cycle in progress
1543
AR Initiation
CB AR cycle initiation
1544
CB ARIP
CB AR cycle in progress
1546
Seq Counter>Set
Sequence counts greater than AR Shots settings
1547
Evolve 3Ph
If a single phase fault evolves to a multi-phase fault during the single phase dead time, this DDB indicates the fault has evolved and that
SPAR will be stopped and 3PAR started.
1550
CB Failed AR
CB AR failed due to persistent fault
1551
DTOK All
Enabling condition for any dead time
1552
DTOK CB 1P
Output DDB indicates conditions to enable single phase autoreclose dead time to run are satisfied
1553
DTOK CB 3P
Output DDB indicates conditions to enable three phase autoreclose dead time to run are satisfied
1554
1P DTime
Indicates single phase autoreclose dead time running
1555
OK Time 3P
OK to start 3PAR dead time
1556
3P DTime1
3Phase dead time 1 running
1557
3P DTime2
3Phase dead time 2 running
1558
3P DTime3
3Phase dead time 3 running
1559
3P DTime4
3Phase dead time 4 running
1560
3P Dtime
Indicates three phase autoreclose dead time running
1565
Set CB Close
Indicates Auto Close signal has been issued
1566
CB Control
B260
SIGNAL NAME
DDB_INHIBIT_LIVE_LINE
DDB_INHIBIT_DEAD_LINE
DDB_INHIBIT_LIVE_BUS1
DDB_INHIBIT_DEAD_BUS1
DDB_CB1_IN_SERVICE
DDB_CB_NO_AR
DDB_TRIP_AR_MEMORY_A
DDB_TRIP_AR_MEMORY_B
DDB_TRIP_AR_MEMORY_C
DDB_AR_START
DDB_AR_IN_PROGRESS
DDB_CB_AR_INIT
DDB_CB_AR_INPROGRESS
DDB_SEQ_COUNT_GREATER_THAN_SHOTS
DDB_EVOLVE_3PHASE
DDB_CB_FAIL_AR
DDB_DEADTIME_OK_ALL
DDB_DEAD_TIME_OK_CB1LSP
DDB_DEAD_TIME_OK_CB1L3P
DDB_SPDT_IN_PROGRESS
DDB_OK_TIME_3POLE
DDB_3POLE_DEAD_TIME1
DDB_3POLE_DEAD_TIME2
DDB_3POLE_DEAD_TIME3
DDB_3POLE_DEAD_TIME4
DDB_CB_3POLE_DEAD_TIME
DDB_SET_CB_CLOSE
DDB_CB_CONTROL
ELEMENT NAME
DESCRIPTION
P54A/B/C/E
P54xMED-TM-EN-1