Cb State Monitoring - GE P4A Technical Manual

Micom p40 agile single br eaker multi-end current differential ied (non distance)
Table of Contents

Advertisement

P54A/B/C/E
6

CB STATE MONITORING

CB State monitoring is used to verify the open or closed state of a circuit breaker. Most circuit breakers have
auxiliary contacts through which they transmit their status (open or closed) to control equipment such as IEDs.
These auxiliary contacts are known as:
52A for contacts that follow the state of the CB
52B for contacts that are in opposition to the state of the CB
This device can be set to monitor both of these types of circuit breaker state indication. If the state is unknown for
some reason, an alarm can be raised.
Some CBs provide both sets of contacts. If this is the case, these contacts will normally be in opposite states.
Should both sets of contacts be open, this would indicate one of the following conditions:
Auxiliary contacts/wiring defective
Circuit Breaker (CB) is defective
CB is in isolated position
Should both sets of contacts be closed, only one of the following two conditions would apply:
Auxiliary contacts/wiring defective
Circuit Breaker (CB) is defective
If any of the above conditions exist, an alarm will be issued after a 5 s time delay. An output contact can be
assigned to this function via the programmable scheme logic (PSL). The time delay is set to avoid unwanted
operation during normal switching duties.
In the CB CONTROL column there is a setting called CB Status Input. This cell can be set at one of the following
four options:
None
52A
52B
Both 52A and 52B
Where None is selected no CB status is available. Where only 52A is used on its own then the device will assume a
52B signal opposite to the 52A signal. Circuit breaker status information will be available in this case but no
discrepancy alarm will be available. The above is also true where only a 52B is used. If both 52A and 52B are used
then status information will be available and in addition a discrepancy alarm will be possible, according to the
following table:
Auxiliary Contact Position
52A
52B
Open
Closed
Closed
Open
Closed
Closed
Open
Open
P54xMED-TM-EN-1
CB State Detected
Breaker open
Breaker closed
CB failure
State unknown
Chapter 12 - Monitoring and Control
Action
Circuit breaker healthy
Circuit breaker healthy
Alarm raised if the condition persists for greater than
5 s
Alarm raised if the condition persists for greater than
5 s
259

Advertisement

Table of Contents
loading

This manual is also suitable for:

P54bP54eP54c

Table of Contents