P54A/B/C/E
ORDINAL
781
ISEF>1 Start
1st stage sensitive earth fault (SEF) overcurrent start
782
ISEF>2 Start
2nd stage sensitive earth fault (SEF) overcurrent start
783
ISEF>3 Start
3rd stage sensitive earth fault (SEF) overcurrent start
784
ISEF>4 Start
4th stage sensitive earth fault (SEF) overcurrent start
785
Thermal Alarm
Thermal Overload Alarm
788
V<1 Start
Undervoltage stage 1, three phase start
789
V<1 Start A/AB
Undervoltage stage 1, A/AB phase start
790
V<1 Start B/BC
Undervoltage stage 1, B/BC phase start
791
V<1 Start C/CA
Undervoltage stage 1, C/CA phase start
792
V<2 Start
Undervoltage stage 2, three phase start
793
V<2 Start A/AB
Undervoltage stage 2, A/AB phase start
794
V<2 Start B/BC
Undervoltage stage 2, B/BC phase start
795
V<2 Start C/CA
Undervoltage stage 2, C/CA phase start
796
V>1 Start
Overvoltage stage 1, three phase start
797
V>1 Start A/AB
Overvoltage stage 1, A/AB phase start
798
V>1 Start B/BC
Overvoltage stage 1, B/BC phase start
799
V>1 Start C/CA
Overvoltage stage 1, C/CA phase start
800
V>2 Start
Overvoltage stage 2, three phase start
801
V>2 Start A/AB
Overvoltage stage 2, A/AB phase start
802
V>2 Start B/BC
Overvoltage stage 2, B/BC phase start
803
V>2 Start C/CA
Overvoltage stage 2, C/CA phase start
804
VN>1 Start
Residual overvoltage stage 1 start
805
VN>2 Start
Residual overvoltage stage 2 start
829
VA< start
Phase A undervoltage level detector used in the pole dead logic. Detectors have a settable threshold: default undervoltage pickup 38.1 V-
drop off 43.8 V
830
VB< start
Phase B undervoltage level detector used in the pole dead logic. Detectors have a settable threshold: default undervoltage pickup 38.1 V-
drop off 43.8 V
831
VC< start
Phase C undervoltage level detector used in the pole dead logic. Detectors have a settable threshold: default undervoltage pickup 38.1 V-
drop off 43.8 V
832
VTS Fast Block
VT supervision fast block - blocks elements which would otherwise maloperate immediately a fuse failure event occurs
833
VTS Slow Block
P54xMED-TM-EN-1
SIGNAL NAME
DDB_SEF_1_START
DDB_SEF_2_START
DDB_SEF_3_START
DDB_SEF_4_START
DDB_THERMAL_ALARM
DDB_PUV_1_3PH_START
DDB_PUV_1_PH_A_START
DDB_PUV_1_PH_B_START
DDB_PUV_1_PH_C_START
DDB_PUV_2_3PH_START
DDB_PUV_2_PH_A_START
DDB_PUV_2_PH_B_START
DDB_PUV_2_PH_C_START
DDB_POV_1_3PH_START
DDB_POV_1_PH_A_START
DDB_POV_1_PH_B_START
DDB_POV_1_PH_C_START
DDB_POV_2_3PH_START
DDB_POV_2_PH_A_START
DDB_POV_2_PH_B_START
DDB_POV_2_PH_C_START
DDB_RESOV_1_START
DDB_RESOV_2_START
DDB_PHASE_A_UNDERVOLTAGE
DDB_PHASE_B_UNDERVOLTAGE
DDB_PHASE_C_UNDERVOLTAGE
DDB_VTS_FAST_BLOCK
DDB_VTS_SLOW_BLOCK
ELEMENT NAME
DESCRIPTION
Appendix B - Settings and Signals