Micom p40 agile single br eaker multi-end current differential ied (non distance)
Table of Contents

Advertisement

P54A/B/C/E
MENU TEXT
Setting that defines third stage overcurrent operating status. Depending on this setting, I>3 will be enabled permanently or in case of
Voltage Transformer Supervision (fuse fail) operation, or in case of communication channel fail, or a combination (and /or) of both.
I>3 Directional
This setting determines the direction of measurement for the third stage overcurrent element.
I>3 Current Set
Pick-up setting for third stage overcurrent element.
I>3 Time Delay
Setting for the operating time-delay for third stage overcurrent element.
I>4 Status
Setting that defines fourth stage overcurrent operating status. Depending on this setting, I>4 will be enabled permanently or in case of
Voltage Transformer Supervision (fuse fail) operation
I>4 Status
Setting that defines fourth stage overcurrent operating status. Depending on this setting, I>4 will be enabled permanently or in case of
Voltage Transformer Supervision (fuse fail) operation, or in case of communication channel fail, or a combination (and /or) of both.
I>4 Directional
This setting determines the direction of measurement for the fourth stage overcurrent element.
I>4 Current Set
Pick-up setting for fourth stage overcurrent element.
I>4 Time Delay
Setting for the operating time-delay for fourth stage overcurrent element.
I> Char Angle
Setting for the IED characteristic angle used for the directional decision. The setting is visible only when 'Directional Fwd' or 'Directional Rev'
is set.
I> Blocking
Logic Settings that determine whether blocking signals from VT supervision affect certain overcurrent stages.
VTS Block – only affects directional overcurrent protection. With the relevant bit set to 1, operation of the Voltage Transformer Supervision
(VTS), will block the stage. When set to 0, the stage will revert to Non-directional upon operation of the VTS.
If I> Status is set 'Enabled VTS', no blocking should be selected in order to provide fault clearance by overcurrent protection during the VTS
condition.
I>1 Usr Rst Char
P54xMED-TM-EN-1
COL
ROW
DEFAULT SETTING
35
14
Directional Fwd
35
15
10
35
16
0
35
18
Disabled
35
18
Disabled
35
19
Non-Directional
35
1A
10
35
1B
0
35
1C
30
35
1D
0xF
35
20
DT
DESCRIPTION
En VTSorCh Fail
En VTSandCh Fail
[Indexed String]
Non-Directional
Directional Fwd
Directional Rev
[Indexed String]
From 0.08*I1 to 32*I1 in steps of 0.01*I1
[Courier Number (current)]
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Disabled
Enabled
Enabled VTS
Enabled Ch Fail
En VTSorCh Fail
En VTSandCh Fail
[Indexed String]
Disabled
Enabled
Enabled VTS
Enabled Ch Fail
En VTSorCh Fail
En VTSandCh Fail
[Indexed String]
Non-Directional
Directional Fwd
Directional Rev
[Indexed String]
From 0.08*I1 to 32*I1 in steps of 0.01*I1
[Courier Number (current)]
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
From -95 to 95 in steps of 1
[Courier Number (angle)]
VTS Blocks I>1
VTS Blocks I>2
VTS Blocks I>3
VTS Blocks I>4
[Binary Flag (16 bits)]
DT
Default Curve 1
Appendix B - Settings and Signals
AVAILABLE OPTIONS
B173