Appendix B - Settings and Signals
ORDINAL
1105
Function Key 10
Function key 10 is activated. In 'Normal' mode it is high on keypress and in 'Toggle' mode remains high/low on single keypress
1024
LED 1
Programmable LED 1
1025
LED 2
Programmable LED 2
1026
LED 3
Programmable LED 3
1027
LED 4
Programmable LED 4
1028
LED 5
Programmable LED 5
1029
LED 6
Programmable LED 6
1030
LED 7
Programmable LED 7
1031
LED 8
Programmable LED 8
1070
LED Cond IN 1
Input to LED Output Condition
1071
LED Cond IN 2
Input to LED Output Condition
1072
LED Cond IN 3
Input to LED Output Condition
1073
LED Cond IN 4
Input to LED Output Condition
1074
LED Cond IN 5
Input to LED Output Condition
1075
LED Cond IN 6
Input to LED Output Condition
1076
LED Cond IN 7
Input to LED Output Condition
1077
LED Cond IN 8
Input to LED Output Condition
1106
CB I^ Maint
Broken current maintenance alarm - circuit breaker cumulative duty alarm set-point
1107
CB I^ Lockout
Broken current lockout alarm - circuit breaker cumulative duty has been exceeded
1108
No.CB OPs Maint
No of circuit breaker operations maintenance alarm - indicated due to circuit breaker trip operations threshold
1109
No.CB OPs Lock
No of circuit breaker operations maintenance lockout - excessive number of circuit breaker trip operations, safety lockout
1110
CB Time Maint
Excessive circuit breaker operating time maintenance alarm - excessive operation time alarm for the circuit breaker (slow interruption time)
1111
CB Time Lockout
Excessive circuit breaker operating time lockout alarm - excessive operation time alarm for the circuit breaker (too slow interruption)
1112
CB FaultFreqLock
Excessive fault frequency lockout alarm
1120
SignalFail Ch1Rx
Reception of messages on channel 1 has stopped
1121
SignalFail Ch1Tx
Transmission of messages on channel 1 has stopped
1124
Ch1 Signal Lost
Mux indicates signal lost over channel 1
1125
Ch1 Path Yellow
One way communication. Local relay that is sending over Ch1 indicates that remote end is not receiving
1130
SignalFail Ch2Rx
Reception of messages on channel 2 has stopped
B252
SIGNAL NAME
DDB_FN_KEY_10
DDB_OUTPUT_LED_1
DDB_OUTPUT_LED_2
DDB_OUTPUT_LED_3
DDB_OUTPUT_LED_4
DDB_OUTPUT_LED_5
DDB_OUTPUT_LED_6
DDB_OUTPUT_LED_7
DDB_OUTPUT_LED_8
DDB_LED_CON_1
DDB_LED_CON_2
DDB_LED_CON_3
DDB_LED_CON_4
DDB_LED_CON_5
DDB_LED_CON_6
DDB_LED_CON_7
DDB_LED_CON_8
DDB_BROKEN_CURRENT_ALARM
DDB_BROKEN_CURRENT_LOCKOUT
DDB_MAINTENANCE_ALARM
DDB_MAINTENANCE_LOCKOUT
DDB_EXCESSIVE_OP_TIME_ALARM
DDB_EXCESSIVE_OP_TIME_LOCKOUT
DDB_EFF_LOCKOUT
DDB_SIGNALLING_FAIL_CH1_RX
DDB_SIGNALLING_FAIL_CH1_TX
DDB_IEEE37_94_CH1_LOSS_OF_SIG
DDB_IEEE37_94_CH1_PATH_YELLOW
DDB_SIGNALLING_FAIL_CH2_RX
ELEMENT NAME
DESCRIPTION
P54A/B/C/E
P54xMED-TM-EN-1

Advertisement

Table of Contents
loading

This manual is also suitable for:

P54bP54eP54c

Table of Contents