GE P4A Technical Manual page 418

Micom p40 agile single br eaker multi-end current differential ied (non distance)
Table of Contents

Advertisement

Chapter 17 - Communications
Direct Operate:
Direct Operate - No Ack:
Count > 1
Pulse On
Pulse Off
Latch On
Latch Off
Queue
Clear Queue
Note: Paired Control points will accept Pulse On/Trip and Pulse On/Close, but only single point will accept the Pulse Off control command.
Reports Binary Input Change Events when no specific variation
requested:
Reports time-tagged Binary Input Change Events when no specific
variation requested:
Sends Unsolicited Responses:
Sends Static Data in Unsolicited Responses:
Default Counter Object/Variation:
Counters Roll Over at:
Sends multi-fragment responses:
Sequential File Transfer Support:
Append File Mode
Custom Status Code Strings
Permissions Field
File Events Assigned to Class
File Events Send Immediately
Multiple Blocks in a Fragment
Max Number of Files Open
7.3.8.2
DNP3 IMPLEMENTATION TABLE
The implementation table provides a list of objects, variations and control codes supported by the device:
Object
Object
Variation
Number
Number
1
0
Binary Input (Variation 0 is used to
request default variation)
1
1
Binary Input
(default - see
note 1)
1
2
Binary Input with Flag
392
Device Profile Document
Function Codes (dec)
Description
1
(read)
22
(assign class)
1
(read)
1
(read)
DNP 3.0
Always
Always
Never
Always
Sometimes
Always
Always
Never
Never
Configurable to send one or the other
Binary input change with time
Never
Never
No other options are permitted
Configurable, Point-by-point list attached
Default object: 20
Default variation: 1
32 bits
Yes
No
No
Yes
No
Yes
No
1
Request
(Library will parse)
Qualifier Codes
(hex)
00, 01
(start-stop)
06
(no range, or all)
07, 08
(limited qty)
17, 27, 28
(index)
00, 01
(start-stop)
06
(no range, or all)
07, 08
(limited qty)
17, 27, 28
(index)
00, 01
(start-stop)
06
(no range, or all)
07, 08
(limited qty)
17, 28
(index)
P54A/B/C/E
Response
(Library will respond with)
Function Codes
Qualifier Codes (hex)
(dec)
129 response
00, 01
(start-stop)
17, 28
(index - see note 2)
129 response
00, 01
(start-stop)
17, 28
(index - see note 2)
P54xMED-TM-EN-1

Advertisement

Table of Contents
loading

This manual is also suitable for:

P54bP54eP54c