GE P4A Technical Manual page 762

Micom p40 agile single br eaker multi-end current differential ied (non distance)
Table of Contents

Advertisement

Appendix B - Settings and Signals
MENU TEXT
This setting enables CB1 to close by manual control when the system satisfies all the System Check Synchronism Stage 2 conditions as listed
under the setting CS2 Status in the SYSTEM CHECKS column.
CB1M SC CS2
This setting enables CB1 to close by manual control when the system satisfies all the System Check Synchronism Stage 2 conditions as listed
under the setting CB1 CS2 Status in the SYSTEM CHECKS column.
CBM SC DLLB
This setting enables CB to close by manual control when the dead line & live bus1 conditions are satisfied as set in the SYSTEM CHECKS
column.
CB1M SC DLLB
This setting enables CB1 to close by manual control when the dead line & live bus1 conditions are satisfied as set in the SYSTEM CHECKS
column.
CBM SC LLDB
This setting enables CB to close by manual control when the live line & dead bus1 conditions are satisfied as set in the SYSTEM CHECKS
column.
CB1M SC LLDB
This setting enables CB1 to close by manual control when the live line & dead bus1 conditions are satisfied as set in the SYSTEM CHECKS
column.
CBM SC DLDB
This setting enables CB to close by manual control when the dead line & dead bus1 conditions are satisfied as set in the SYSTEM CHECKS
column.
CB2M SC LLDB
This setting enables CB2 to close by manual control when the live line & dead bus2 conditions are satisfied as set in the SYSTEM CHECKS
column.
CB2M SC DLDB
This setting enables CB2 to close by manual control when the dead line & dead bus2 conditions are satisfied as set in the SYSTEM CHECKS
column.
Num CBs
Setting defines which CB(s) are active for the specific installation: CB1 only, CB2 only or both CB1 & CB2.
Num CBs
If the Num CBs setting (cell 4950 {above} in the AUTORECLOSE column) is set to CB1 Only, or CB2 Only, then this setting determines which
auto-reclose modes are permitted for the circuit breaker : single phase (AR 1P) only, both single phase and three phase (AR 1/3P), three phase
only (AR 3P), or the auto-reclosing mode is controlled by opto input signals (AR Opto) mapped via DDB's (1497) AR Mode 1P and (1498) AR
Mode 3P.
AR Mode
B196
COL
ROW
DEFAULT SETTING
48
B4
Disabled
48
B5
Disabled
48
B5
Disabled
48
B6
Disabled
48
B6
Disabled
48
B7
Disabled
48
BC
Disabled
48
BD
Disabled
49
50
CB1 Only
49
50
CB1 Only
49
51
AR 3P
DESCRIPTION
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
CB1 Only
CB2 Only
CB1&CB2
[Courier Number]
CB1 Only
CB2 Only
CB1&CB2
[Courier Number]
AR 1P
AR 1/3P
AR 3P
AR Opto
P54A/B/C/E
AVAILABLE OPTIONS
P54xMED-TM-EN-1