P54A/B/C/E
MENU TEXT
Setting for the tripping characteristic for the second stage negative sequence overcurrent element.
I2>2 Directional
This setting determines the direction of measurement for this element.
I2>2 Current Set
Pick-up setting for the second stage negative sequence overcurrent element.
I2>2 Time Delay
Setting for the operating time-delay for the second stage negative sequence overcurrent element.
I2>2 TMS
Setting for the time multiplier setting to adjust the operating time of the IEC IDMT characteristic.
I2>2 Time Dial
Setting for the time multiplier setting to adjust the operating time of the IEEE/US IDMT curves.
I2>2 Reset Char
Setting to determine the type of reset/release characteristic of the IEEE/US curves.
I2>2 tRESET
Setting that determines the reset/release time for definite time reset characteristic.
I2>3 Status
Setting to enable or disable the third stage negative sequence element.
I2>3 Directional
This setting determines the direction of measurement for this element.
I2>3 Current Set
Pick-up setting for the third stage negative sequence overcurrent element.
I2>3 Time Delay
Setting for the operating time-delay for the third stage negative sequence overcurrent element.
I2>4 Status
Setting to enable or disable the fourth stage negative sequence element.
I2>4 Directional
This setting determines the direction of measurement for this element.
I2>4 Current Set
Pick-up setting for the fourth stage negative sequence overcurrent element.
P54xMED-TM-EN-1
COL
ROW
DEFAULT SETTING
36
22
Non-Directional
36
25
0.2
36
27
10
36
28
1
36
29
1
36
2C
DT
36
2D
0
36
30
Disabled
36
32
Non-Directional
36
35
0.2
36
37
10
36
40
Disabled
36
42
Non-Directional
36
45
0.2
DESCRIPTION
IEC E Inverse
UK LT Inverse
IEEE M Inverse
IEEE V Inverse
IEEE E Inverse
US Inverse
US ST Inverse
[Indexed String]
Non-Directional
Directional Fwd
Directional Rev
[Indexed String]
From 0.08*I1 to 4*I1 in steps of 0.01*I1
[Courier Number (current)]
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
From 0.025 to 1.2 in steps of 0.005
[Courier Number (decimal)]
From 0.01 to 100 in steps of 0.01
[Courier Number (decimal)]
DT
Inverse
[Indexed String]
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Disabled
Enabled
[Indexed String]
Non-Directional
Directional Fwd
Directional Rev
[Indexed String]
From 0.08*I1 to 32*I1 in steps of 0.01*I1
[Courier Number (current)]
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Disabled
Enabled
[Indexed String]
Non-Directional
Directional Fwd
Directional Rev
[Indexed String]
From 0.08*I1 to 32*I1 in steps of 0.01*I1
[Courier Number (current)]