Autoreclose Internal Signals - GE P4A Technical Manual

Micom p40 agile single br eaker multi-end current differential ied (non distance)
Table of Contents

Advertisement

P54A/B/C/E
4.2

AUTORECLOSE INTERNAL SIGNALS

The following table lists all the internal signals used in the CB control and Autoreclose logic system:
Signal Name
3PDTCOMP
3-phase AR Dead Time (25)
AR DISABLED
AR Enabled (5)
BAR CB1
Autoreclose Lockout (55)
CB1 3PDTCOMP
3-phase AR Dead Time (25)
CB1 AROK
AR OK (8)
CB1 ARSUCC
Successful AR Signals (36)
CB1 LARIP
AR In Progress (16)
CB1 Op1P
CB Open (3)
CB1 Op2/3P
CB Open (3)
CB1 OpAny
CB Open (3)
CB1 SPOK
Force 3-phase Trip (10)
CB1CRLO
CB In Service (4)
3-phase AR Cycle Selection
CB1L3PAR
(21)
CB1L3PAROK
AR Modes Enable (9)
1-phase AR Cycle Selection
CB1LSPAR
(19)
CB1LSPAROK
AR Modes Enable (9)
CB1SPDTCOMP
Dead Time Start Enable (22)
CBARCancel
Reclaim Time (35)
P54xMED-TM-EN-1
Source Module
3-phase AR Dead Time (25)
Force 3-phase Trip (10)
1-pole / 3-pole Trip (13)
AR Reset Successful (37)
Reset CB Lockout (57)
AR OK (8)
CB Autoclose (32)
Prepare Reclaim Initiation (34)
CB Healthy and System Check
Timers (39)
AR In Progress (16)
AR In Progress (16)
AR Reset Successful (37)
1-phase AR Cycle Selection (19)
3-phase AR Cycle Selection (21)
Reclaim Time (35)
Dead Time Start Enable (22)
CB Autoclose (32)
Successful AR Signals (36)
AR In Progress (16)
3-phase AR Cycle Selection (21)
1-phase AR Dead Time (24)
Successful AR Signals (36)
AR In Progress (16)
AR Reset Successful (37)
Autoreclose Lockout (55)
Reset CB Lockout (57)
1-phase AR Cycle Selection (19)
3-phase AR Dead Time (25)
CB Autoclose (32)
AR In Progress (16)
3-phase AR Cycle Selection (21)
Autoreclose Lockout (55)
1-phase AR Dead Time (24)
CB Healthy and System Check
Timers (39)
Force 3-phase Trip (10)
1-phase AR Cycle Selection (19)
3-phase AR Cycle Selection (21)
Autoreclose Lockout (55)
CB Autoclose (32)
Prepare Reclaim Initiation (34)
CB Healthy and System Check
Timers (39)
AR In Progress (16)
Destination Module
Chapter 7 - Autoreclose
Description
Three phase dead time complete
Overall Autoreclosing disabled
Block Autoreclose
Three-pole Autoreclose dead time is complete
CB is OK for Autoreclose
Autoreclose successful
CB Autoreclose in progress
CB is open on 1 phase
CB is open on 2 or 3 phases
CB is open on 1, 2 or 3 phases
CB is OK for single-phase Autoreclose
Reset CB lockout
Three-phase Autoreclose is active
CB is OK to perform three-phase Autoreclose
Single-phase Autoreclose is in progress
CB is OK to perform single-phase Autoreclose
CB single-phase dead time is complete
Cancel CB Autoreclose
139