Current Differential Protection; Current Differential Bias Characteristic; Lower Slope; Figure 206: Current Differential Bias Characteristics - GE P4A Technical Manual

Micom p40 agile single br eaker multi-end current differential ied (non distance)
Table of Contents

Advertisement

P54A/B/C/E
10

CURRENT DIFFERENTIAL PROTECTION

10.1

CURRENT DIFFERENTIAL BIAS CHARACTERISTIC

1.
In the CONFIGURATION column, disable all protection elements other than the one being tested.
2.
Make a note of which elements need to be re-enabled after testing.
3.
Set the device to loopback mode, isolating it from the remote end.
4.
Connect the test circuit shown below. Alternatively, use an injection test set to supply Ia and Ib
L
N
V01452

Figure 206: Current Differential Bias Characteristics

10.1.1

LOWER SLOPE

If three LEDs have been assigned to provide phase segregated trip information (Trip A, Trip B and Trip C), these may
be used to indicate correct operation per-phase. If LEDs are not used, use monitor options, as follows.
1.
Go to COMMISSION TESTS > Monitor Bit. Change cells 1, 2 and 3 to the values 523, 524 and 525 respectively.
The Test Port Status cell then displays the status of Trip Output A (DDB 523), Trip Output B (DDB 524) and
Trip Output C (DDB 525), with the rightmost bit representing Phase A Trip. From now on monitor the Test
Port Status cell.
2.
Make sure that the IED is in loopback mode by setting the Loopback Mode cell to External and applying a
loop-back, either by direct fibre or using a P59x. Alternatively you can set the Test Loopback cell to
Internal.
3.
Adjust the variac and the resistor to give a bias current of 1pu in the A-phase (1A into terminals 3-2 for 1A
applications, or 5A into terminals 1-2 for 5A applications).
The device trips, contacts associated with the A-phase operate, and bit 1 (rightmost) of the Test Port Status
cell is set to 1. Some LEDs, including the yellow alarm LED, switch OFF, but ignore these for the moment.
4.
When the current in the A Phase is established, close the switch and slowly increase the current in the B
phase from zero until Phase B trips (bit 2 of the Test Port Status cell is set to 1).
For the initial conditions where the magnitude of the bias current in phase A = 1 pu, record the phase B current
magnitude and check that it corresponds to the following.
Connection type
2-terminal & dual redundant
3-terminal
Assumption: Is1 = 0.2 pu, k1 = 30%, Is2 = 2.0 pu
For other differential settings or current injected into A phase (Ia), the following formula can be used (enter slope in
pu form, which is. percentage/100):
Connection type
2-terminal & dual redundant
P54xMED-TM-EN-1
Chapter 20 - Commissioning Instructions
Ra
Rb
Magnitude of differential current in phase B
0.25 pu +/-10%
0.216 pu +/-10%
Magnitude of differential current in phase B
0.5 x (Is1 + (Ia x k1)) pu +/- 10%
P54x IED
Ia
A
Ph a
Ib
A
Ph b
475