GE P4A Technical Manual page 806

Micom p40 agile single br eaker multi-end current differential ied (non distance)
Table of Contents

Advertisement

Appendix B - Settings and Signals
ORDINAL
To enable SOTF logic by an external pulse. When this input is energized by en external pulse, SOTF becomes enabled during "SOTF Pulse"
time setting
509
RP1 Read Only
Enables RP1 Read Only
510
RP2 Read Only
Enables RP2 Read Only
511
NIC Read Only
Enables NIC Read Only
522
Any Trip
Any trip signal - can be used as the trip command in three-pole tripping applications
523
Trip Output A
Trip signal for phase A - used as a command to drive trip A output contact(s). Takes the output from the internal trip conversion logic
524
Trip Output B
Trip signal for phase B - used as a command to drive trip B output contact(s). Takes the output from the internal trip conversion logic
525
Trip Output C
Trip signal for phase C - used as a command to drive trip C output contact(s). Takes the output from the internal trip conversion logic
526
Trip 3ph
Trip signal for 3ph - used as a command to drive trip 3ph output contact(s). Takes the output from the internal trip conversion logic
527
2/3 Ph Fault
2 or 3 phase fault indication - used to flag whether the fault is polyphase. Typically used to control auto-reclose logic, where auto-reclosing
is allowed only for single phase faults
528
3 Ph Fault
3 phase fault indication. Typically used to control auto-reclose logic, where auto-reclosing is blocked for faults affecting all three phases
together
528
3 Ph Fault
3 phase fault indication. Typically used to control auto-reclose logic, where auto-reclosing is blocked for faults affecting all three phases
together
529
Trip Inputs 3Ph
Trip 3 phase - input to trip latching logic
530
Trip Inputs A
A phase trip - input to trip conversion logic. Essential to ensure correct single or three pole trip command results (e.g. converts a 2 pole trip to
3 phase)
531
Trip Inputs B
B phase trip - input to trip conversion logic. Essential to ensure correct single or three pole trip command results (e.g. converts a 2 pole trip to
3 phase)
532
Trip Inputs C
C phase trip - input to trip conversion logic. Essential to ensure correct single or three pole trip command results (e.g. converts a 2 pole trip to
3 phase)
533
Force 3Pole Trip
External DDB input to host protection trip conversion logic to force 3 Pole tripping of CB for all faults
534
External Trip3ph
External trip 3 phase - allows external protection to initiate breaker fail, circuit breaker condition monitoring statistics, and internal auto-
reclose (if enabled)
535
External Trip A
External trip A phase - allows external protection to initiate breaker fail, circuit breaker condition monitoring statistics, and internal auto-
reclose (if enabled)
536
External Trip B
External trip B phase - allows external protection to initiate breaker fail, circuit breaker condition monitoring statistics, and internal auto-
reclose (if enabled)
537
External Trip C
External trip C phase - allows external protection to initiate breaker fail, circuit breaker condition monitoring statistics, and internal auto-
reclose (if enabled)
542
SG Select x1
Setting group selector X1 (low bit)-selects SG2 if only DDB 542 signal is active.
SG1 is active if both DDB 542 & DDB 543=0
SG4 is active if both DDB 542 & DDB 543=1
543
SG Select 1x
Setting group selector 1X (high bit)-selects SG3 if only DDB 543 is active.
B240
SIGNAL NAME
DDB_REMOTEREADONLY_RP1
DDB_REMOTEREADONLY_RP2
DDB_REMOTEREADONLY_NIC
DDB_ANY_TRIP
DDB_TRIP_A_PHASE
DDB_TRIP_B_PHASE
DDB_TRIP_C_PHASE
DDB_TRIP_3PH
DDB_TR_23_PHASE_FAULT
DDB_TR_3_PHASE_FAULT
DDB_TR_3_PHASE_FAULT
DDB_TR_3_PHASE
DDB_TR_A_PHASE
DDB_TR_B_PHASE
DDB_TR_C_PHASE
DDB_FORCE_3_POLE_TRIP
DDB_EXTERNAL_TRIP_3PH
DDB_EXTERNAL_TRIP_A
DDB_EXTERNAL_TRIP_B
DDB_EXTERNAL_TRIP_C
DDB_SG_SELECTOR_X1
DDB_SG_SELECTOR_1X
ELEMENT NAME
DESCRIPTION
P54A/B/C/E
P54xMED-TM-EN-1