Appendix B - Settings and Signals
MENU TEXT
Setting for the tripping characteristic for the second stage earth fault overcurrent element.
IN>2 Directional
This setting determines the direction of measurement for first stage element.
IN>2 Current Set
Pick-up setting for second stage overcurrent element
IN2>1 IDG Is
This setting is set as a multiple of "IN>" setting for the IDG curve (Scandinavian) and determines the actual IED current threshold at which the
element starts.
IN>2 Time Delay
Setting for the time-delay for the definite time setting if selected for second stage element. The setting is available only when DT function is
selected.
IN>2 TMS
Setting for the time multiplier setting to adjust the operating time of the IEC IDMT characteristic.
IN>2 Time Dial
Setting for the time multiplier setting to adjust the operating time of the IEEE/US IDMT curves. The Time Dial (TD) is a multiplier on the
standard curve equation, in order to achieve the required tripping time. The reference curve is based on TD = 1.
Care: Certain manufacturer's use a mid-range value of TD = 5 or 7, so it may be necessary to divide by 5 or 7 to achieve parity.
IN2>1 IDG Time
Setting for the IDG curve used to set the minimum operating time at high levels of fault current.
IN>2 Reset Char
Setting to determine the type of reset/release characteristic of the IEEE/US curves.
IN>2 tRESET
Setting that determines the reset/release time for definite time reset characteristic.
IN>3 Status
Setting that defines third stage overcurrent operating status. Depending of this setting, IN>3 will be enabled permanently or in case of
Voltage Transformer Supervision (fuse fail) operation
IN>3 Status
B178
COL
ROW
DEFAULT SETTING
38
37
Non-Directional
38
3A
0.2
38
3B
1.5
38
3D
1
38
3E
1
38
3F
1
38
41
1.2
38
43
DT
38
44
0
38
46
Disabled
38
46
Disabled
DESCRIPTION
UK LT Inverse
IEEE M Inverse
IEEE V Inverse
IEEE E Inverse
US Inverse
US ST Inverse
IDG
Default Curve 1
Default Curve 2
Default Curve 3
Default Curve 4
[Indexed String]
Non-Directional
Directional Fwd
Directional Rev
[Indexed String]
From 0.08*I1 to 4.0*I1 in steps of 0.01*I1
[Courier Number (current)]
From 1 to 4 in steps of 0.1
[Courier Number (decimal)]
From 0 to 200 in steps of 0.01
[Courier Number (time-seconds)]
From 0.025 to 1.2 in steps of 0.005
[Courier Number (decimal)]
From 0.01 to 100 in steps of 0.01
[Courier Number (decimal)]
From 1 to 2 in steps of 0.01
[Courier Number (time-seconds)]
DT
Inverse
[Indexed String]
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Disabled
Enabled
Enabled VTS
Enabled Ch Fail
En VTSorCh Fail
En VTSandCh Fail
[Indexed String]
Disabled
Enabled
Enabled VTS
Enabled Ch Fail
En VTSorCh Fail
P54A/B/C/E
AVAILABLE OPTIONS
P54xMED-TM-EN-1