P54A/B/C/E
MENU TEXT
V<1 Voltage Set
Sets the pick-up setting for first stage undervoltage element.
V<1 Time Delay
Setting for the operating time-delay for the first stage definite time undervoltage element.
V<1 TMS
Setting for the time multiplier setting to adjust the operating time of the IDMT characteristic.
V<1 Poledead Inh
If the cell is enabled, the relevant stage will become inhibited by the pole dead logic. This logic produces an output when it detects either an
open circuit breaker via auxiliary contacts feeding the IED opto inputs or it detects a combination of both undercurrent and undervoltage on
any one phase. It allows the undervoltage protection to reset when the circuit breaker opens to cater for line or bus side VT applications.
V<2 Status
Setting to enable or disable the second stage undervoltage element.
V<2 Voltage Set
This setting determines the pick-up setting for second stage undervoltage element.
V<2 Time Delay
Setting for the operating time-delay for the second stage definite time undervoltage element.
V<2 Poledead Inh
If the cell is enabled, the relevant stage will become inhibited by the pole dead logic. This logic produces an output when it detects either an
open circuit breaker via auxiliary contacts feeding the IED opto inputs or it detects a combination of both undercurrent and undervoltage on
any one phase. It allows the undervoltage protection to reset when the circuit breaker opens to cater for line or bus side VT applications.
OVERVOLTAGE
Over Voltage Sub Heading
V> Measur't Mode
Sets the combination of measured input voltage that will be used for the overvoltage elements.
Note: If any stage is disabled, the associated text in the setting menu cell setting will remain visible but will not affect the operation of the
stage that is enabled.
V> Operate Mode
Setting that determines whether any phase or all three phases has to satisfy the overvoltage criteria before a decision is made.
Note: If any stage is disabled, the associated text in the setting menu cell setting will remain visible but will not affect the operation of the
stage that is enabled.
V>1 Function
Setting for the tripping characteristic of the first stage overvoltage element.
V>1 Voltage Set
Sets the pick-up setting for first stage overvoltage element.
V>1 Time Delay
Setting for the operating time-delay for the first stage definite time overvoltage element.
P54xMED-TM-EN-1
COL
ROW
DEFAULT SETTING
42
05
80
42
06
10
42
07
1
42
08
Enabled
42
09
Disabled
42
0A
60
42
0B
5
42
0C
Enabled
42
0D
42
0E
V>1 & V>2 Ph-Ph
42
0F
V>1 & V>2 Any Ph
42
10
DT
42
11
130
42
12
10
DESCRIPTION
From 10*V1 to 120*V1 in steps of 1*V1
[Courier Number (voltage)]
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
From 0.5 to 100 in steps of 0.5
[Courier Number (decimal)]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
From 10*V1 to 120*V1 in steps of 1*V1
[Courier Number (voltage)]
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Disabled
Enabled
[Indexed String]
V>1 & V>2 Ph-Ph
V>1 & V>2 Ph-N
V>1Ph-Ph V>2Ph-N
V>1Ph-N V>2Ph-Ph
[Indexed String]
V>1 & V>2 Any Ph
V>1 & V>2 3 Phase
V>1AnyPh V>2 3Ph
V>1 3Ph V>2AnyPh
[Indexed String]
Disabled
DT
IDMT
[Indexed String]
From 60*V1 to 185*V1 in steps of 1*V1
[Courier Number (voltage)]
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Appendix B - Settings and Signals