GE P4A Technical Manual page 767

Micom p40 agile single br eaker multi-end current differential ied (non distance)
Table of Contents

Advertisement

P54A/B/C/E
MENU TEXT
Setting that determines impact of the second stage sensitive earth fault overcurrent protection on AR operation.
ISEF>3 AR
Setting that determines impact of the third stage sensitive earth fault overcurrent protection on AR operation.
ISEF>4 AR
Setting that determines impact of the fourth stage sensitive earth fault overcurrent protection on AR operation.
Neutral Diff AR
Setting that determines impact of the Neutral Differential protection on AR operation.
AR SYS CHECKS
System Checks Sub Heading
CB SC all
This setting determines whether a system check (e.g. live bus / dead line etc) is required for any auto-reclose of CB. If Enabled, system check
is required for some or all reclosures. If Disabled, system check is not required for any reclosures.
CB1L SC all
This setting determines whether a system check (e.g. live bus / dead line etc) is required for any auto-reclose of CB1 as leader. If Enabled,
system check is required for some or all reclosures. If Disabled, system check is not required for any reclosures.
CB SC Shot 1
This setting determines whether a system check (e.g. live bus / dead line etc) is required for the first shot reclosure of CB. If Enabled, system
check is required for the first shot reclosure. If Disabled, system check is not required for the first shot reclosure.
CB1L SC Shot 1
This setting determines whether a system check (e.g. live bus / dead line etc) is required for the first shot reclosure of CB1 as leader. If
Enabled, system check is required for the first shot reclosure. If Disabled, system check is not required for the first shot reclosure.
CB SC ClsNoDly
If CB SC ClsNoDly is Enabled, CB can reclose as leader as soon as the synchro check conditions are satisfied, without waiting for the dead
time to elapse.
This option is sometimes required for the second line end to reclose onto a line with delayed auto-reclosing (typical cycle: first line end
recloses after the dead time with
live bus & dead line, then the second line end recloses immediately with live bus & live line in synchronism).
CB1L SC ClsNoDly
If CB1L SC ClsNoDly is Enabled, CB1 can reclose as leader as soon as the synchro check conditions are satisfied, without waiting for the dead
time to elapse.
This option is sometimes required for the second line end to reclose onto a line with delayed auto-reclosing (typical cycle: first line end
recloses after the dead time with
live bus & dead line, then the second line end recloses immediately with live bus & live line in synchronism).
CB SC CS1
This setting enables CB to auto-reclose as leader when the system satisfies all the System Check Synchronism Stage 1 criteria as defined
under CB CS1 Status settings in the SYSTEM CHECKS column.
CB1L SC CS1
P54xMED-TM-EN-1
COL
ROW
DEFAULT SETTING
49
86
No Action
49
87
No Action
49
88
Initiate AR
49
A5
49
A6
Disabled
49
A6
Disabled
49
A7
Disabled
49
A7
Disabled
49
A8
Disabled
49
A8
Disabled
49
A9
Disabled
49
A9
Disabled
DESCRIPTION
No Action
Initiate AR
Block AR
[Indexed String]
No Action
Initiate AR
Block AR
[Indexed String]
Initiate AR
Block AR
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Appendix B - Settings and Signals
AVAILABLE OPTIONS
B201