GE P4A Technical Manual page 761

Micom p40 agile single br eaker multi-end current differential ied (non distance)
Table of Contents

Advertisement

P54A/B/C/E
MENU TEXT
bus voltages (refer to setting CS2 Slip Freq)
CB1 CS2 SlipCtrl
Setting to enable or disable blocking of synchronism check stage 2 for reclosing CB1 by excessive frequency difference (slip) between line
and bus voltages (refer to setting CB1 CS2 SlipFreq)
CS2 Slip Freq
If CS2 Slip Ctrl is enabled, synchronism check stage 2 is blocked for reclosing CB if measured frequency difference between line and bus
voltages is greater than this setting.
CB1 CS2 SlipFreq
If CB1 CS2 SlipCtrl is enabled, synchronism check stage 2 is blocked for reclosing CB1 if measured frequency difference between line and bus
voltages is greater than this setting.
CS2 Adaptive
Setting to enable or disable Adaptive CB closing with System Check Synchronism stage 2 closing for CB: logic uses set CB CI Time to issue CB
close command at such a time that the predicted phase angle difference when CB main contacts touch is as close as possible to 0 degrees.
If Adaptive closing is disabled, the logic issues CB close command as soon as phase angle comes within set limit at CB CS2 Angle .
CB1 CS2 Adaptive
Setting to enable or disable Adaptive CB closing with System Check Synchronism stage 2 closing for CB1: logic uses set CB1 CI Time to issue
CB1 close command at such a time that the predicted phase angle difference when CB1 main contacts touch is as close as possible to 0
degrees. If Adaptive closing is disabled, the logic issues CB1 close command as soon as phase angle comes within set limit at CB1 CS2 Angle
.
CB Cl Time
This sets CB closing time, from receipt of CB close command until main contacts touch.
CB1 Cl Time
This sets CB1 closing time, from receipt of CB1 close command until main contacts touch.
Sys Checks CB2
Setting to enable or disable both stages of system checks for reclosing CB2.
If Sys Checks CB2 is set to Disabled, all other menu settings associated with synchronism checks for CB2 become invisible, and a DDB (1484)
signal SChksInactiveCB2 is set.
CBM SC required
This setting determines whether a system check (e.g. live bus / dead line etc) is required for any manual (operator-controlled) closure of CB. If
Enabled, system check is required for closure. If Disabled, system check is not required.
CB1M SC required
This setting determines whether a system check (e.g. live bus / dead line etc) is required for any manual (operator-controlled) closure of CB1.
If Enabled, system check is required for closure. If Disabled, system check is not required.
CBM SC CS1
This setting enables CB to close by manual control when the system satisfies all the System Check Synchronism Stage 1 conditions as listed
under the setting CS1 Status in the SYSTEM CHECKS column.
CB1M SC CS1
This setting enables CB1 to close by manual control when the system satisfies all the System Check Synchronism Stage 1 conditions as listed
under the setting CB1 CS1 Status in the SYSTEM CHECKS column.
CBM SC CS2
P54xMED-TM-EN-1
COL
ROW
DEFAULT SETTING
48
97
Enabled
48
98
0.05
48
98
0.05
48
99
Disabled
48
99
Disabled
48
9A
0.05
48
9A
0.05
48
9B
Disabled
48
B2
Disabled
48
B2
Disabled
48
B3
Disabled
48
B3
Disabled
48
B4
Disabled
DESCRIPTION
Disabled
Enabled
[Indexed String]
From 0.005 to 2 in steps of 0.005
[Courier Number (frequency)]
From 0.005 to 2 in steps of 0.005
[Courier Number (frequency)]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
From 0.01 to 0.5 in steps of 0.001
[Courier Number (time-seconds)]
From 0.01 to 0.5 in steps of 0.001
[Courier Number (time-seconds)]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
Appendix B - Settings and Signals
AVAILABLE OPTIONS
B195