Sensitive Earth Fault Protection; Sef Protection Implementation; Epatr B Curve - GE P4A Technical Manual

Micom p40 agile single br eaker multi-end current differential ied (non distance)
Table of Contents

Advertisement

P54A/B/C/E
5

SENSITIVE EARTH FAULT PROTECTION

With some earth faults, the fault current flowing to earth is limited by either intentional resistance (as is the case
with some HV systems) or unintentional resistance (e.g. in very dry conditions and where the substrate is high
resistance, such as sand or rock).
To provide protection in such cases, it is necessary to provide an earth fault protection system with a setting that is
considerably lower than for normal line protection. Such sensitivity cannot be provided with conventional CTs,
therefore the SEF input would normally be fed from a core balance current transformer (CBCT) mounted around
the three phases of the feeder cable. The SEF transformer should be a special measurement class transformer.
5.1

SEF PROTECTION IMPLEMENTATION

The product provides four stages of SEF protection with independent time delay characteristics.
Stages 1, 2 provide a choice of operate and reset characteristics, where you can select between:
A range of IDMT (Inverse Definite Minimum Time) curves
DT (Definite Time)
This is achieved using the cells
ISEF>(n) Function for the overcurrent operate characteristic
ISEF>(n) Reset Chr for the overcurrent reset characteristic
where (n) is the number of the stage.
Stages 1 and 2 also provide a Timer Hold facility. This is configured using the cells ISEF>(n) tReset.
Stages 3 and 4 have definite time characteristics only.
Each stage can be individually inhibited with a DDB signal Inhibit ISEF>(n), where n is the stage number.
5.2

EPATR B CURVE

The EPATR B curve is commonly used for time-delayed Sensitive Earth Fault protection in certain markets. This
curve is only available in the Sensitive Earth Fault protection stages 1 and 2. It is based on primary current settings,
employing a SEF CT ratio of 100:1 A.
The EPATR_B curve has 3 separate segments defined in terms of the primary current. It is defined as follows:
Segment
1
ISEF = 0.5A to 6.0A
2
ISEF = 6.0A to 200A
3
ISEF above 200A
where TMS (time multiplier setting) is 0.025 - 1.2 in steps of 0.025.
P54xMED-TM-EN-1
Primary Current Range Based on 100A:1A CT Ratio
Chapter 9 - Current Protection Functions
Current/Time Characteristic
t = 432 x TMS/ISEF 0.655 secs
t = 800 x TMS/ISEF secs
t = 4 x TMS secs
207

Advertisement

Table of Contents
loading

This manual is also suitable for:

P54bP54eP54c

Table of Contents