P54A/B/C/E
MENU TEXT
characters.
The community name setting must be the same in both the SNMP Manager and the IED.
COMMISSION TESTS
This column contains commissioning test settings
Opto I/P Status
This menu cell displays the status of the available IED's opto-isolated inputs as a binary string, a '1' indicating an energized opto-isolated
input and a '0' a de-energized one.
Relay O/P Status
This menu cell displays the status of the digital data bus (DDB) signals that result in energization of the available output relays as a binary
string, a '1' indicating an operated state and '0' a non-operated state.
When the 'Test Mode' cell is set to 'Enabled' the 'Relay O/P Status' cell does not show the current status of the output relays and hence can
not be used to confirm operation of the output relays. Therefore it will be necessary to monitor the state of each contact in turn.
Test Port Status
This menu cell displays the status of the eight digital data bus (DDB) signals that have been allocated in the 'Monitor Bit' cells.
Monitor Bit 1
The eight 'Monitor Bit' cells allow the user to select the status of which digital data bus signals can be observed in the 'Test Port Status' cell or
via the monitor/download port.
Monitor Bit 2
The eight 'Monitor Bit' cells allow the user to select the status of which digital data bus signals can be observed in the 'Test Port Status' cell or
via the monitor/download port.
Monitor Bit 3
The eight 'Monitor Bit' cells allow the user to select the status of which digital data bus signals can be observed in the 'Test Port Status' cell or
via the monitor/download port.
Monitor Bit 4
The eight 'Monitor Bit' cells allow the user to select the status of which digital data bus signals can be observed in the 'Test Port Status' cell or
via the monitor/download port.
Monitor Bit 5
The eight 'Monitor Bit' cells allow the user to select the status of which digital data bus signals can be observed in the 'Test Port Status' cell or
via the monitor/download port.
Monitor Bit 6
The eight 'Monitor Bit' cells allow the user to select the status of which digital data bus signals can be observed in the 'Test Port Status' cell or
via the monitor/download port.
Monitor Bit 7
The eight 'Monitor Bit' cells allow the user to select the status of which digital data bus signals can be observed in the 'Test Port Status' cell or
via the monitor/download port.
Monitor Bit 8
The eight 'Monitor Bit' cells allow the user to select the status of which digital data bus signals can be observed in the 'Test Port Status' cell or
via the monitor/download port.
IED Test Mode
The IED Test Mode menu cell is used to allow online testing to be performed on the IED without operation of the trip contacts. It also enables
a facility to directly test the output contacts by applying menu controlled test signals.
This setting influences the processing of control service frames with an IEC61850 Test mode flag. It does not influence the processing of
other incoming data, such as GOOSE.
To select test mode the IED Test Mode menu cell should be set to 'Test', which takes the IED out of service. It also causes an alarm condition
P54xMED-TM-EN-1
COL
ROW
DEFAULT SETTING
0F
00
0F
01
0F
02
0F
03
0F
05
1060
0F
06
1062
0F
07
1064
0F
08
1066
0F
09
1068
0F
0A
1070
0F
0B
1072
0F
0C
1074
0F
0D
Disabled
DESCRIPTION
Opto I/P Status
[Binary Flag (32) Indexed String]
Relay O/P Status
[Binary Flag (32) Indexed String]
Test Port Status
[Binary Flag (8) Indexed String]
From 0 to 2047 in steps of 1
[Unsigned Integer (16 bits)]
From 0 to 2047 in steps of 1
[Unsigned Integer (16 bits)]
From 0 to 2047 in steps of 1
[Unsigned Integer (16 bits)]
From 0 to 2047 in steps of 1
[Unsigned Integer (16 bits)]
From 0 to 2047 in steps of 1
[Unsigned Integer (16 bits)]
From 0 to 2047 in steps of 1
[Unsigned Integer (16 bits)]
From 0 to 2047 in steps of 1
[Unsigned Integer (16 bits)]
From 0 to 2047 in steps of 1
[Unsigned Integer (16 bits)]
Disabled
Test Mode
Contacts Blocked
[Indexed String]
Appendix B - Settings and Signals