MENU TEXT
V>1 TMS
Setting for the time multiplier setting to adjust the operating time of the IDMT characteristic.
V>2 Status
Setting to enable or disable the second stage overvoltage element.
V>2 Voltage Set
This setting determines the pick-up setting for the second stage overvoltage element.
V>2 Time Delay
Setting for the operating time-delay for the second stage definite time overvoltage element.
COMP OVERVOLTAGE
Compensated Over Voltage Sub Heading
V1>1 Cmp Funct
Tripping characteristic setting for the first stage compensated overvoltage element.
V1>1 Cmp Vlt Set
Sets the pick-up setting for first stage overvoltage element. This is set in terms of the phase to neutral voltage.
V1>1 Cmp Tim Dly
Setting for the operating time-delay for the first stage definite time compensated overvoltage element.
V1>1 Cmp TMS
Setting for the time multiplier setting to adjust the operating time of the IDMT characteristic.
V1>2 Cmp Status
Setting to enable or disable the second stage compensated overvoltage element.
V1>2 Cmp Vlt Set
This setting determines the pick-up setting for the second stage overvoltage element.
V1>2 Cmp Tim Dly
Setting for the operating time-delay for the second stage definite time compensated overvoltage element.
GROUP 1: FREQ
PROTECTION
This column contains settings for Frequency
UNDER FREQUENCY
Under frequency Sub Heading
F<1 Status
Setting to enable or disable the first stage underfrequency element.
F<1 Setting
Setting that determines the pick-up threshold for the first stage underfrequency element.
F<1 Time Delay
Setting that determines the minimum operating time-delay for the first stage underfrequency element.
F<2 Status
Setting to enable or disable the second stage underfrequency element.
F<2 Setting
B186
COL
ROW
DEFAULT SETTING
42
13
1
42
14
Disabled
42
15
150
42
16
0.5
42
20
42
23
Disabled
42
24
75
42
25
10
42
26
1
42
27
Disabled
42
28
85
42
29
0.5
43
00
43
01
43
02
Enabled
43
03
49.5
43
04
4
43
05
Disabled
43
06
49
DESCRIPTION
From 0.5 to 100 in steps of 0.5
[Courier Number (decimal)]
Disabled
Enabled
[Indexed String]
From 60*V1 to 185*V1 in steps of 1*V1
[Courier Number (voltage)]
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Disabled
DT
IDMT
[Indexed String]
From 60*V1 to 110*V1 in steps of 1*V1
[Courier Number (voltage)]
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
From 0.5 to 100 in steps of 0.5
[Courier Number (decimal)]
Disabled
Enabled
[Indexed String]
From 60*V1 to 110*V1 in steps of 1*V1
[Courier Number (voltage)]
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Disabled
Enabled
[Indexed String]
From 45 to 65 in steps of 0.01
[Courier Number (frequency)]
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Disabled
Enabled
[Indexed String]
From 45 to 65 in steps of 0.01
[Courier Number (frequency)]