GE P4A Technical Manual page 759

Micom p40 agile single br eaker multi-end current differential ied (non distance)
Table of Contents

Advertisement

P54A/B/C/E
MENU TEXT
Bus is considered Live with voltage above this setting.
Live Bus 1
Bus 1 is considered Live with voltage above this setting.
Dead Bus
Bus is considered Dead with voltage below this setting.
Dead Bus 1
Bus 1 is considered Dead with voltage below this setting.
Live Bus 2
Bus 2 is considered Live with voltage above this setting.
CS OV
Check Synch Overvoltage setting decides that System Check Synchronism logic for CB1 is blocked if V> is one of the selected options in
setting CB1 CS Volt.Blk (48 8E), and either line or bus voltage is above this setting.
System Check Synchronism for CB2 is blocked if V> is one of the selected options in setting CB2 CS Volt. Blk (48 9C), and either line or bus
voltage is above this setting.
System Checks
Setting to enable or disable both stages of system checks for reclosing.
If System Checks is set to Disabled, all other menu settings associated with synchronism checks become invisible, and a DDB (880) signal
SysChks Inactive is set.
Sys Checks CB1
Setting to enable or disable both stages of system checks for reclosing CB1
If Sys Checks CB1 is set to Disabled, all other menu settings associated with synchronism checks for CB1 become invisible, and a DDB (880)
signal SChksInactiveCB1 is set.
CS Voltage Block
Setting to determine which, if any, conditions should block synchronism check (undervoltage V<, overvoltage V>, and/or voltage differential
Vdiff etc) for the line and bus voltages.
CB1 CS Volt. Blk
Setting to determine which, if any, conditions should block synchronism check for CB1 (undervoltage V<, overvoltage V>, and/or voltage
differential Vdiff etc) for the line and bus voltages.
CS1 Status
Setting to enable or disable the stage 1 synchronism check elements for auto-reclosing and manual closing of CB.
CB1 CS1 Status
Setting to enable or disable the stage 1 synchronism check elements for auto-reclosing and manual closing CB1.
P54xMED-TM-EN-1
COL
ROW
DEFAULT SETTING
48
87
32
48
88
13
48
88
13
48
89
32
48
8C
130
48
8D
Disabled
48
8D
Disabled
48
8E
V<
48
8E
V<
48
8F
Enabled
48
8F
Enabled
DESCRIPTION
From 5 to 132 in steps of 0.5
[Courier Number (voltage)]
From 5 to 132 in steps of 0.5
[Courier Number (voltage)]
From 5 to 132 in steps of 0.5
[Courier Number (voltage)]
From 5 to 132 in steps of 0.5
[Courier Number (voltage)]
From 60 to 200 in steps of 0.5
[Courier Number (voltage)]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
None
V<
V>
Vdiff>
V< and V>
V< and Vdiff>
V> and Vdiff>
V< V> and Vdiff>
[Indexed String]
None
V<
V>
Vdiff>
V< and V>
V< and Vdiff>
V> and Vdiff>
V< V> and Vdiff>
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Appendix B - Settings and Signals
AVAILABLE OPTIONS
B193