MENU TEXT
ITU- G8.21 and detailed in following cells
Ch1 No.Errored s
Displays the number of seconds containing 1 or more errored or lost messages over channel 1
Ch1 No.Sev Err s
Displays the number of seconds containing 31 or more errored or lost messages over channel 1. Any severely errored seconds are ignored
when working out the minutes intervals
Ch1 No.Dgraded m
Displays the number of minutes containing 2 or more errored or lost messages over channel 1
Ch2 No.Vald Mess
Same as for channel 1
Ch2 No.Err Mess
Same as for channel 1
Ch2 No.Errored s
Same as for channel 1
Ch2 No.Sev Err s
Same as for channel 1
Ch2 No.Dgraded m
Same as for channel 1
MaxCh1 PropDelay
Displays the maximum value of the channel 1 overall propagation delay divided by 2 when the protection communications are enabled.
MaxCh2 PropDelay
Same as for channel 1
Clear Statistics
The error statistics are automatically cleared on power-up. They can also be cleared using the Clear Statistics setting in Measurements
column of the menu.
Ch1 L-R2 PropDly
Channel 1 propagation time is displayed in seconds. These times are the ones calculated with asynchronous sampling (some times called
"ping pong" method).
Ch2 L-R2 PropDly
Same as for channel 1
Ch1 L-R3 PropDly
Channel 1 propagation time is displayed in seconds. These times are the ones calculated with asynchronous sampling (some times called
"ping pong" method).
Ch2 L-R3 PropDly
Same as for channel 1
Ch1 L-R4 PropDly
Channel 1 propagation time is displayed in seconds. These times are the ones calculated with asynchronous sampling (some times called
"ping pong" method).
Ch2 L-R4 PropDly
Same as for channel 1
Ch1 L-R5 PropDly
B22
COL
ROW
DEFAULT SETTING
05
15
05
16
05
17
05
18
05
19
05
1A
05
1B
05
1C
05
26
05
27
05
30
No
05
31
05
32
05
33
05
34
05
35
05
36
05
37
DESCRIPTION
Ch1 No.Errored s
[Unsigned Integer (32 bits)]
Ch1 No.Sev Err s
[Unsigned Integer (32 bits)]
Ch1 No.Dgraded m
[Unsigned Integer (32 bits)]
Ch2 No.Vald Mess
[Unsigned Integer (32 bits)]
Ch2 No.Err Mess
[Unsigned Integer (32 bits)]
Ch2 No.Errored s
[Unsigned Integer (32 bits)]
Ch2 No.Sev Err s
[Unsigned Integer (32 bits)]
Ch2 No.Dgraded m
[Unsigned Integer (32 bits)]
MaxCh1 PropDelay
[Courier Number (time-seconds)]
MaxCh2 PropDelay
[Courier Number (time-seconds)]
No
Yes
[Indexed String]
Ch1 L-R2 PropDly
[Courier Number (time-seconds)]
Ch2 L-R2 PropDly
[Courier Number (time-seconds)]
Ch1 L-R3 PropDly
[Courier Number (time-seconds)]
Ch2 L-R3 PropDly
[Courier Number (time-seconds)]
Ch1 L-R4 PropDly
[Courier Number (time-seconds)]
Ch2 L-R4 PropDly
[Courier Number (time-seconds)]
Ch1 L-R5 PropDly
[Courier Number (time-seconds)]
P54A/B/C/E