Direct Connection; Indirect Connection - GE P4A Technical Manual

Micom p40 agile single br eaker multi-end current differential ied (non distance)
Table of Contents

Advertisement

P54A/B/C/E
1550 nm single-mode
1550 nm single-mode
850 nm
850 nm
850 nm
1300 nm multi-mode
1300 nm single-mode
1550 nm single-mode
2.6.1

DIRECT CONNECTION

If you are using direct fibre connections, IEEE C37.94 protocol will be used at 12 channels of 64kbps. you need to
set the Scheme Setup settings and you are advised to change the Address setting from the default. You find these
settings in the PROT COMMS/IM64 columns. You should not need to use any of the other settings that would be
applicable if using shared links and/or interfacing units.
2.6.2

INDIRECT CONNECTION

For 850nm communications links where the connection is not direct fibre, IEEE C37.94 protocol option is available
to interface with standard telecommunications equipment supporting the IEEE C37.94 interface.
An 850nm fibre-optic interface can connect directly to a multiplexer supporting the IEEE C37.94 standard. 850 nm
multi-mode optical fibres, either 50/125 mm or 62.5/125 m are suitable. BFOC/2.5 type fibre optic connectors are
used.
The IEEE C37.94 standard defines an N*64 kbits/s selection, where N is a number between 1 and 12 and selects
the channel used in the multiplexer. For multi-ended line differential, the communication is always 12 channels to
allow optimum protection performance.
P54xMED-TM-EN-1
Ch 1
Chapter 15 - Fibre Teleprotection
Not fitted
1550 nm single-mode
1300 nm multi-mode
1300 nm single-mode
1550 nm single-mode
850 nm
850 nm
850 nm
Ch2