GE P4A Technical Manual page 723

Micom p40 agile single br eaker multi-end current differential ied (non distance)
Table of Contents

Advertisement

P54A/B/C/E
MENU TEXT
IEC 61850 versions only. The Publisher Sim cell allows the simulation bit to be sent in the GOOSE message, for example for testing or
commissioning.
When 'Disabled' is selected, the simulation bit for the goose control block is not set.
When 'Enabled' is selected, the simulation bit for the goose control block is set.
Once testing is complete the cell must be set back to 'Disabled' to restore the GOOSE scheme back to normal service.
Note: The cell 'Test Mode' under IED Configurator used in software prior to IEC 61850 Edition 2 has been renamed as 'Publisher Sim'
Ignore Test Flag
IEC61850 versions only. The Test Mode cell allows the test pattern to be sent in the GOOSE message, for example for testing or
commissioning. When 'Disabled' is selected, the test flag is not set. When 'Pass Through' is selected, the test flag is set, but the data in the
GOOSE message is sent as normal. When 'Forced' is selected, the test flag is set, and the data sent in the GOOSE message is as per the 'VOP
Test Pattern' setting below. Once testing is complete the cell must be set back to 'Disabled' to restore the GOOSE scheme back to normal
service.
PROT COMMS/ IM64
This column contains settings for Current Differential/IM64 Configuration
No. of Junctions
Number Of Junction In the Power System Scheme being protected
No. of Junctions
Number Of Junction In the Power System Scheme being protected
No. of Terminals
Number of Terminal (IEDs) being used
No. of Terminals
Communication Address for each of the IEDs in the scheme. Each letter is the IED address within a scheme.
Scheme Address
Communication Address for each of the IEDs in the scheme. The number is the scheme number.
Terminal Address
Terminal Address
Terminal Address
Terminal Address for P541 only
Clock Source Ch1
Setting that defines which clock source is used to synchronize data transmissions over channel 1. The setting will depend on
communications configuration and external clock source availability. If IED's are connected direct fibre over channel 1, 'Internal' setting
should be selected. If channel 1 is routed via a multiplexer, either setting may be required (see Application Notes).
Clock Source Ch2
Setting that defines which clock source is used to synchronize data transmissions over channel 2. The setting will depend on
communications configuration and external clock source availability. If IED's are connected direct fibre over channel 2, 'Internal' setting
should be selected. If channel 2 is routed via a multiplexer, either setting may be required (see Application Notes).
P54xMED-TM-EN-1
COL
ROW
DEFAULT SETTING
19
73
No
20
00
20
70
1
20
70
1
20
71
2 Terminal
20
71
2 Terminal
20
72
1
20
73
A
20
73
A
20
74
Internal
20
75
Internal
DESCRIPTION
No
Yes
[Indexed String]
2 Junctions
3 Junctions
4 Junctions
[Indexed String]
2 Junctions
3 Junctions
4 Junctions
[Indexed String]
Dual Redundant
3 Terminals
4 Terminals
5 Terminals
6 Terminals
[Indexed String]
Dual Redundant
3 Terminals
4 Terminals
5 Terminals
6 Terminals
[Indexed String]
From 1 to 16 in steps of 1
[Indexed String]
From 0 to 5 in steps of 1
[Indexed String]
0 or 1
[Indexed String]
Internal
External
[Indexed String]
Internal
External
[Indexed String]
Appendix B - Settings and Signals
AVAILABLE OPTIONS
B157