GE P4A Technical Manual page 600

Micom p40 agile single br eaker multi-end current differential ied (non distance)
Table of Contents

Advertisement

Appendix B - Settings and Signals
MENU TEXT
To invert polarity (180 °) of the SEF CT
M CT Polarity
To invert polarity (180 °) of the Mutual CT
VT Connected
To indicate if voltage transformers are connected to the IED. This MUST be set properly to ensure Pole Dead logic works correctly. If set to
'No', it will set VTS Slow Block and VTS Fast Block DDB's, but will not raise any alarms. It will also override the VTS enabled setting should the
user set it. If set to 'Yes' this setting will have no effect.
CS VT Ph Shift
Phase angle difference between selected phase ("C/S Input" 0A 0F) of Line VT input and applied "CB CS" VT input voltage under healthy
system conditions
CS VT Mag
Ratio of voltage magnitudes of selected phase ("C/S Input" 0A 0F) of Line VT input and applied "CB CS" VT input voltage under healthy system
conditions
RECORD CONTROL
This column contains settings for Record Controls
Alarm Event
Disabling this setting means that no event is generated for alarms
Relay O/P Event
Disabling this setting means that no event will be generated for any change in logic output state.
Opto Input Event
Disabling this setting means that no event will be generated for any change in logic input state.
General Event
Disabling this setting means that no General Events are generated
Fault Rec Event
Disabling this setting means that no event will be generated for any fault that produces a fault record
Maint Rec Event
Disabling this setting means that no event will be generated for any occurrence that produces a maintenance record.
Protection Event
Disabling this setting means that any operation of protection elements will not be logged as an event
Flt Rec Extended
When this setting is disabled, the fault record contains a snap shot of the local, remote, differential and bias currents taken 1 cycle after the
trip.
With this setting enabled an additional snap shot of local, remote, differential and bias currents taken at the time the differential trips is
included in the fault record.
DDB 31 - 0
Chooses whether any individual DDB's should be deselected as a stored event, by setting the relevant bit to 0 (zero). Typically used for
B34
COL
ROW
DEFAULT SETTING
0A
14
Standard
0A
18
Yes
0A
21
0
0A
22
1
0B
00
0B
04
Enabled
0B
05
Enabled
0B
06
Enabled
0B
07
Enabled
0B
08
Enabled
0B
09
Enabled
0B
0A
Enabled
0B
2F
Disabled
0B
40
0xFFFFFFFF
DESCRIPTION
Standard
Inverted
[Indexed String]
No
Yes
[Indexed String]
From -180 to 180 in steps of 5
[Courier Number (angle)]
From 0.2 to 3 in steps of 0.01
[Courier Number]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
Disabled
Enabled
[Indexed String]
High order word of long stored in 1st register
Low order word of long stored in 2nd register
[Binary Flag (32-Bit)]
P54A/B/C/E