GE P4A Technical Manual page 743

Micom p40 agile single br eaker multi-end current differential ied (non distance)
Table of Contents

Advertisement

P54A/B/C/E
MENU TEXT
Setting for the tripping characteristic for the first stage earth fault overcurrent element.
IN>1 Directional
This setting determines the direction of measurement for first stage element.
IN>1 Current Set
Pick-up setting for first stage overcurrent element
IN1>1 IDG Is
This setting is set as a multiple of "IN>" setting for the IDG curve (Scandinavian) and determines the actual IED current threshold at which the
element starts.
IN>1 Time Delay
Setting for the time-delay for the definite time setting if selected for first stage element. The setting is available only when DT function is
selected.
IN>1 TMS
Setting for the time multiplier setting to adjust the operating time of the IEC IDMT characteristic.
IN>1 Time Dial
Setting for the time multiplier setting to adjust the operating time of the IEEE/US IDMT curves. The Time Dial (TD) is a multiplier on the
standard curve equation, in order to achieve the required tripping time. The reference curve is based on TD = 1.
Care: Certain manufacturer's use a mid-range value of TD = 5 or 7, so it may be necessary to divide by 5 or 7 to achieve parity.
IN1>1 IDG Time
Setting for the IDG curve used to set the minimum operating time at high levels of fault current.
IN>1 Reset Char
Setting to determine the type of reset/release characteristic of the IEEE/US curves.
IN>1 tRESET
Setting that determines the reset/release time for definite time reset characteristic.
IN>2 Status
Setting that defines second stage overcurrent operating status. Depending of this setting, IN>2 will be enabled permanently or in case of
Voltage Transformer Supervision (fuse fail) operation
IN>2 Status
Setting that defines second stage overcurrent operating status. Depending of this setting, IN>2 will be enabled permanently or in case of
Voltage Transformer Supervision (fuse fail) operation, or in case of communication channel fail, or a combination (and /or) of both.
IN>2 Function
P54xMED-TM-EN-1
COL
ROW
DEFAULT SETTING
38
26
Non-Directional
38
29
0.2
38
2A
1.5
38
2C
1
38
2D
1
38
2E
1
38
30
1.2
38
32
DT
38
33
0
38
35
Disabled
38
35
Disabled
38
36
IEC S Inverse
DESCRIPTION
Default Curve 2
Default Curve 3
Default Curve 4
[Indexed String]
Non-Directional
Directional Fwd
Directional Rev
[Indexed String]
From 0.08*I1 to 4.0*I1 in steps of 0.01*I1
[Courier Number (current)]
From 1 to 4 in steps of 0.1
[Courier Number (decimal)]
From 0 to 200 in steps of 0.01
[Courier Number (time-seconds)]
From 0.025 to 1.2 in steps of 0.005
[Courier Number (decimal)]
From 0.01 to 100 in steps of 0.01
[Courier Number (decimal)]
From 1 to 2 in steps of 0.01
[Courier Number (time-seconds)]
DT
Inverse
[Indexed String]
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Disabled
Enabled
Enabled VTS
Enabled Ch Fail
En VTSorCh Fail
En VTSandCh Fail
[Indexed String]
Disabled
Enabled
Enabled VTS
Enabled Ch Fail
En VTSorCh Fail
En VTSandCh Fail
[Indexed String]
DT
IEC S Inverse
IEC V Inverse
IEC E Inverse
Appendix B - Settings and Signals
AVAILABLE OPTIONS
B177

Advertisement

Table of Contents
loading