P54A/B/C/E
V01056
Figure 186: Edition 2 system - backward compatibility
An Edition 2 IED cannot normally operate within an Edition 1 IEC 61850 system. An Edition 2 IED can work for
GOOSE messaging in a mixed system, providing the client is compatible with Edition 2.
V01057
Figure 187: Edition 1 system - forward compatibility issues
7.4.11.2
EDITION-2 COMMON DATA CLASSES
The following common data classes (CDCs) are new to Edition 2 and therefore should not be used in GOOSE control
blocks in mixed Edition 1 and Edition 2 systems
Histogram (HST)
●
●
Visible string status (VSS)
Object reference setting (ORG)
●
Controllable enumerated status (ENC)
●
Controllable analogue process value (APC)
●
Binary controlled analogue process value (BAC)
●
●
Enumerated status setting (ENG)
Time setting group (TSG)
●
P54xMED-TM-EN-1
Chapter 17 - Communications
405