Figure 186: Edition 2 system - backward compatibility

An Edition 2 IED cannot normally operate within an Edition 1 IEC 61850 system. An Edition 2 IED can work for
GOOSE messaging in a mixed system, providing the client is compatible with Edition 2.
V01057

Figure 187: Edition 1 system - forward compatibility issues

7.4.11.2
EDITION-2 COMMON DATA CLASSES
The following common data classes (CDCs) are new to Edition 2 and therefore should not be used in GOOSE control
blocks in mixed Edition 1 and Edition 2 systems
Histogram (HST)
Visible string status (VSS)
Object reference setting (ORG)
Controllable enumerated status (ENC)
Controllable analogue process value (APC)
Binary controlled analogue process value (BAC)
Enumerated status setting (ENG)
Time setting group (TSG)