Ct Compensation; Figure 42: Ct Compensation - GE P4A Technical Manual

Micom p40 agile single br eaker multi-end current differential ied (non distance)
Table of Contents

Advertisement

Chapter 6 - Current Differential Protection
6

CT COMPENSATION

The primary and secondary ratios for the phase current transformers are set in the CT AND VT RATIOS column.
These settings are used to display the phase current quantities in the MEASUREMENTS 1 column. The device can
be set to display the input current either in primary values or in secondary values.
To ensure correct operation of the differential elements, it is important that under load and through fault
conditions, the currents into the differential elements of the devices balance. If the CTs have different ratios this will
not be the case. This product has CT ratio correction (magnitude compensation) to overcome this problem.
When calculating differential and bias currents, the devices use per-unit (p.u.) quantities. CT ratio compensation is
used to scale-up the current signals to match those of the remote terminals by setting an appropriate value in the
Ph CT Corr'tion setting in the CURRENT DIFF column. Because of dynamic limitations, this scaled-up value is
limited to 40 p.u. Values exceeding this are clipped at 40 p.u.
Similarly compensated per-unit values are used in the calculation of the differential and bias currents.
The per-unit compensated values of local and remote currents as well as the per-unit values of differential and
bias currents are scaled-down by the local CT ratio correction factor and displayed in the MEASUREMENTS 3
column.
The process is outlined in the figure below:
Secondary CT
I
[Amps sec.]
ABC
* 1 / I
* CT_Ratio
V02609

Figure 42: CT Compensation

112
rating
I
[p.u.]
LOCAL
CT rated
I 
[p.u.]
LOCAL
I 
[p.u.]
REMOTE
1
I 
[p.u.]
REMOTE
2
* 1 / CT_Correction
Primary or
* I
Secondary CT
CT rated
rating
Measurements 3
40 p.u. clipping
*
CT_Correction
I 
[p.u.]
DIFF
I 
[p.u.]
BIAS
Settings
[Amps pri. or sec .]
* 1 / I
Primary or
Secondary CT
rating
P54A/B/C/E
I 
[p.u.]
LOCAL
Trip, Intertrip
Settings [p.u.]
CT rated
P54xMED-TM-EN-1

Advertisement

Table of Contents
loading

This manual is also suitable for:

P54bP54eP54c

Table of Contents