Application Notes; Undervoltage Setting Guidelines - GE P4A Technical Manual

Micom p40 agile single br eaker multi-end current differential ied (non distance)
Table of Contents

Advertisement

Chapter 10 - Voltage Protection Functions
open circuit breaker via auxiliary contacts feeding the opto-inputs or it detects a combination of both
undercurrent and undervoltage on any one phase.
2.3

APPLICATION NOTES

2.3.1

UNDERVOLTAGE SETTING GUIDELINES

In most applications, undervoltage protection is not required to operate during system earth fault conditions. If this
is the case you should select phase-to-phase voltage measurement, as this quantity is less affected by single-
phase voltage dips due to earth faults.
The voltage threshold setting for the undervoltage protection should be set at some value below the voltage
excursions that may be expected under normal system operating conditions. This threshold is dependent on the
system in question but typical healthy system voltage excursions may be in the order of 10% of nominal value.
The same applies to the time setting. The required time delay is dependent on the time for which the system is able
to withstand a reduced voltage.
If motor loads are connected, then a typical time setting may be in the order of 0.5 seconds.
226