Appendix B - Settings and Signals
MENU TEXT
Reset the CB condition counters.
CB Monitoring
Displays the status of the CB Condition monitoring alarms
CB CONTROL
This column controls the circuit Breaker Control configuration
CB Control by
Selects the type of circuit breaker control to be used
Close Pulse Time
Defines the duration of the close pulse within which CB should close when close command is issued. If CB fails to close after elapse of this
time, CB close fail alarm is set.
Trip Pulse Time
Defines the duration of the trip pulse within which CB should trip when manual or protection trip command is issued. If CB does not trip
within set Trip Pulse Time, CB failed to trip alarm is set.
Man Close Delay
This defines the delay time before the close pulse is executed.
CB Healthy Time
Settable time delay for manual closure with this circuit breaker check. If the circuit breaker does not indicate a healthy condition in this time
period following a close command then the IED will lockout and alarm. CB Healthy is required for manual and auto reclosure.
Check Sync Time
A user settable time delay is included for manual closure with System Check Synchronizing. If the System Check Synchronizing criteria are
not satisfied in this time period following a close command the IED will lockout and alarm.
CB mon LO reset
Command to reset the CB monitoring Lockout Alarm
Rst CB mon LO by
This setting is used to decide preferred option to reset a lockout condition caused by CB monitoring conditions either by a manual circuit
breaker close command or via the user interface.
CB mon LO RstDly
B24
COL
ROW
DEFAULT SETTING
06
10
07
00
07
01
Disabled
07
02
0.5
07
03
0.5
07
05
10
07
06
5
07
07
5
07
08
No
07
09
CB Close
07
0A
5
DESCRIPTION
Yes
[Indexed String]
I^ Maint Alarm
I^ Lockout Alarm
CB OPs Maint
CB OPs Lock
CB Time Maint
CB Time Lockout
Fault Freq Lock
I^ Maint Alarm
I^ Lockout Alarm
CB2 OPs Maint
CB2 OPs Lock
CB2 Time Maint
CB2 Time Lockout
Fault Freq Lock
[Binary Flag (14) & Indexed String]
Disabled
Local
Remote
Local+Remote
Opto
Opto+local
Opto+Remote
Opto+Rem+local
[Indexed String]
From 0.1 to 50 in steps of 0.01
[Courier Number (time-seconds)]
From 0.1 to 50 in steps of 0.01
[Courier Number (time-seconds)]
From 0.01 to 600 in steps of 0.01
[Courier Number (time-seconds)]
From 0.01 to 9999 in steps of 0.01
[Courier Number (time-seconds)]
From 0.01 to 9999 in steps of 0.01
[Courier Number (time-seconds)]
No
Yes
[Indexed String]
User Interface
CB Close
[Indexed String]
From 0.1 to 600 in steps of 0.01
[Courier Number (time-seconds)]
P54A/B/C/E
AVAILABLE OPTIONS
P54xMED-TM-EN-1