Making the EtherNet/IP Connection Settings with the Sysmac
Studio
This section describes the procedure to make the EtherNet/IP connection settings with the Sysmac Stu-
dio.
Here, we take the following system configuration as an example to describe how to set the EtherNet/IP
connection settings.
Example: System that connects the built-in EtherNet/IP port on Controller 1 and the built-in EtherNet/IP
port on Controller 2 via Ethernet
• Set the settings so that values in the network variable Net_Out1 allocated for Controller 2 are sent to
the network variable Net_In1 allocated for Controller 1 at the set RPI of 50 ms cycle.
• This example assumes the programs for both Controllers 1 and 2 are registered in the same project.
Originator device
Controller 1
(NY512-1500:
Built-in EtherNet/IP
port)
Originator device tag set
Net_In1
Net_In1
Convert the network variable to the tag.
Network variable
(Network Publish attribute: Input)
Net_In1
(Data type: WORD)
A-10
Sysmac Studio
Controllers 1 and 2 are respectively named as follows and registered in the same project.
· Controller_1 (Controller 1: NY512-1500 (Built-in EtherNet/IP port))
· Controller_2 (Controller 2: NJ501-1500)
EtherNet/IP
Target device tag set
(Tag set)
(Tag)
Network variable
(Network Publish attribute: Output)
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User's Manual (W563)
Project on the Sysmac Studio
Target device
Controller 2
CJ1W-EIP21
(NJ501-1500)
(NJ)
Net_Out1
(Tag set)
(Tag)
Net_Out1
Net_Out1
(Data type: WORD)