Accessing via a Relay Node
Example: Communicating from Controller 1 to Controller 3 via Controller 2
Controller 1
Communica-
tions port
Built-in
(#02)
EtherNet/IP port
Built-in
EtherNet/IP
port
(1) Controller 1 to Controller 2
• Network type number: "#02" (Output the command via EtherNet/IP port.)
• Remote address:
(2) Controller 2 to EtherNet/IP Unit 2
• Network type number: "#01" (Output the command via internal backplane port.)
• Remote address:
12 hex))
(3) EtherNet/IP Unit 2 to EtherNet/IP Unit 3
• Network type number: "#02" (Output the command via EtherNet/IP port.)
• Remote address:
(4) EtherNet/IP Unit 3 to Controller 3
• Network type number: "#01" (Output the command via internal backplane port.)
• Remote address:
Route path
 When Routing the Output from the Controller to Windows in an Industrial PC
NY-series Industrial PC
Controller
Communications
port (#03)
• Network type number: "#03" (Output the command via internal port.)
• Destination address: Specify the destination IP address
• Route path: 03\192.168.254.2
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User's Manual (W563)
Controller 2
EtherNet/IP Unit 2
Backplane
IP address:
port #01
192.168.250.2
EtherNet/IP
port
Specify the remote IP address.
"#12" (Unit address of EtherNet/IP Unit (Unit number: 2+10 hex =
Specify the remote IP address.
"#00" (unit address of Controller)
02\192.168.250.2\01\#12\02\192.168.257.3\01\#00
:
(1)
Windows
IP address:
192.168.254.2
Internal port
8 CIP Message Communications
Controller 3
Unit address
00 hex
Unit address
12 hex
Communications
port (#02)
(2)
(3)
(4)
EtherNet/IP Unit 3
Backplane
port #01
IP address:
192.168.257.3
EtherNet/IP port
8-9