14 Checking Communications Status of Network and Troubleshooting
Connection status
General
Additional
Status
Status
(hex)
(hex)
01
0108
Error code returned from target:
Attempted to open a connection with
an unsupported connection type.
01
0109
Error code returned from target:
The connection size settings are dif-
ferent in the originator and target.
01
0110
Error code returned from target:
The target was unable to open the
connection, because of its operating
status, such as downloading set-
tings.
01
0111
Error code returned from target:
The RPI was set to a value that
exceeds the specifications.
01
0113
Error code generated by originator
or returned from target:
Attempted to open more connec-
tions than allowed by the specifica-
tions (32).
01
0114
Error code returned from target:
The Vendor ID and Product Code
did not match when opening con-
nection.
01
0115
Error code returned from target:
The Product Type did not match
when opening connection.
01
0116
Error code returned from target:
The Major/Minor Revisions did not
match when opening connection.
01
0117
Error code returned from target:
The tag set specified in the connec-
tion's target variables does not exist.
14-10
Source of error
Configuration 1
This error does not
occur.
Check the connection sizes set in the originator and target.
Check whether the
tag data link is
stopped at the tar-
get. (Restart the tag
data link communi-
cations with the soft-
ware switch.)
This error does not
occur.
Check the connec-
tion settings (number
of connections) at
the originator and
target.
This error does not
occur.
This error does not
occur.
Check the major and
minor revisions set
for the target device
and connection. If
necessary, obtain
the most recent EDS
file and set it again.
Check whether the
originator and target
tag sets and tags are
set correctly.
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User's Manual (W563)
Handling
Configuration 2
Configuration 3
Check which connec-
Check which connec-
tion types can be used
tion types can be used
by the target. (Contact
by the originator. (An
the manufacturer.) Only
error will occur if a con-
multicast and point-to-
nection other than a
point connections can
multicast or point-to-
be set.
point connection is set.)
Depends on the tar-
Check whether the tag
get's specifications.
data link is stopped at
(Contact the target
the target. (Restart the
device's manufacturer.)
tag data link communi-
cations with the soft-
ware switch.)
Check the target's RPI
Set the originator's RPI
setting specifications.
setting to 10 seconds
or less.
Check the connection
Check the connection
settings (number of
settings (number of
connections) at the
connections) at the
originator and target.
originator and target.
Check the connection
Check the connection
specifications for
specifications for
devices from other
devices from other
manufacturers.
manufacturers.
Depends on the tar-
Check the originator's
get's specifications.
connection settings.
(Contact the target
device's manufac-
turer.) Check that the
target device's EDS file
is correct.
Depends on the tar-
Check the originator's
get's specifications.
connection settings.
(Contact the target
device's manufac-
turer.) Check that the
target device's EDS file
is correct.
Depends on the tar-
Check the originator's
get's specifications.
connection settings.
(Contact the target
device's manufac-
turer.) Check that the
target device's EDS file
is correct.
Depends on the tar-
Check the originator's
get's specifications.
connection settings.
(Contact the target
Check whether the tar-
device's manufacturer.)
get tag sets and tags
are set correctly.

Advertisement