The settings are as follows:
Setting
Connection I/O Type
Connection Type
The Connection Structure Area and the following items are not displayed if the Hide Detail Button is clicked.
Packet Interval (RPI)
Timeout Value
Connection Name
2
After you make all of the settings, click the OK Button.
 Editing Settings for All Connections
You can edit the connection settings between the originator and all of the target devices selected in
the Register Device List together in a table.
1
Click the Connections Tab, and then click the Edit All Button. The following Edit All Connec-
tions Dialog Box is displayed.
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User's Manual (W563)
Select Input Only (tag type) to use tag data links with a CS1W-EIP21, CJ1W-EIP21,
CJ2B-EIP21, CJ2M-EIP21, CJ1W-EIP21(CJ2), CJ1W-EIP21(NJ), NX701, NJ501-
, NJ301-, NJ101, or NY52. When you create tag data links for other
devices, select the connection I/O type specified in that device's EDS file. Use the Input
Only (ID type) setting when another company's node is the originator and does not sup-
port connection settings with a Tag type setting.
Select whether the data is sent in multi-cast or unicast (point-to-point) format. The
default setting is multi-cast.
• Multi-cast connection:
• Point-to-Point connection:
Note Refer to 7-1-4 Overview of Operation for details on using multi-cast and unicast
connections, and counting the number of connections.
Set the data update cycle (i.e., the packet interval) of each connection between the
originator and target. The default setting is 50 ms (i.e., data is updated once every 50
ms).
Set the RPI to between 1 and 10,000 ms in 1-ms increments.
Set the time until a connection timeout is detected. The timeout value is set as a multi-
ple of the packet interval (RPI) and can be set to 4, 8, 16, 32, 64, 128, 256, or 512 times
the packet interval. The default setting is 4 times the packet interval (RPI).
Set a name for the connection. (32 single-byte characters max.)
7 Tag Data Link Functions
Description
Select when the same data is shared by multiple nodes.
This setting is usually used.
Select when the same data is not shared by multiple
nodes. In a unicast transmission, other nodes are not
burdened with an unnecessary load.
7
7-35