14-2 Connection Status Codes and
Troubleshooting
This section explains how to identify and correct errors based on the tag data link's connection status.
The connection status can be read using the Connection Tab Page of the Network Configurator's Mon-
itor Device Window. Refer to 14-1 Device Monitoring on the Network Configurator for details.
Additional Information
The connection status has the same meaning as the Connection Manager's General and Addi-
tional error response codes, as defined in the CIP specifications.
The following table shows the likely causes of the errors causes for each configuration and connection
status (code).
Configuration 1
Configuration 2
Configuration 3
Connection status
General
Additional
Status
Status
(hex)
(hex)
00
0000
Normal status code:
The connection has been opened
and the tag data link is communicat-
ing normally.
01
0100
Error code returned from target:
Attempted to open multiple connec-
tions for the same connection.
01
0103
Error code returned from target:
Attempted to open a connection with
an unsupported transport class.
01
0106
Duplicate consumers:
Attempted to open multiple connec-
tions for single-consumer data.
01
0107
Error code returned from target:
Attempted to close a connection, but
that connection was already closed.
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User's Manual (W563)
14 Checking Communications Status of Network and Troubleshooting
Originator
CS1W-EIP21, CJ1W-EIP21, CJ2H-CPU-
EIP, CJ2M-CPU3, NJ501-, NJ301-
, NJ101-, and NX701-
, NY52-
CS1W-EIP21, CJ1W-EIP21, CJ2H-CPU-
EIP, CJ2M-CPU3, NJ501-, NJ301-
, NJ101-, and NX701-
, NY52-
Products from other manufacturers
Source of error
CS1W-EIP21, CJ1W-EIP21, CJ2H-
CPU-EIP, CJ2M-CPU3, NJ501-
, NJ301-, NJ101-,
and NX701-, NY52-
Products from other manufacturers
CS1W-EIP21, CJ1W-EIP21, CJ2H-
CPU-EIP, CJ2M-CPU3, NJ501-
, NJ301-, NJ101-,
and NX701-, NY52-
Handling
Configuration 1
Configuration 2
---
---
This error does not
Depends on the tar-
occur.
get's specifications.
(This error should not
occur. If is does, con-
tact the target device's
manufacturer.)
This error does not
Confirm that the target
occur.
supports Class 1.
If the tag data link is
Depends on the tar-
stopped or started,
get's specifications.
this error may occur
(Contact the target
according to the tim-
device's manufacturer.)
ing, but the system
will recover automat-
ically.
This error does not
This error does not
occur.
occur.
Target
Configuration 3
---
Depends on the origi-
nator's specifications.
(This error should not
occur. If is does, con-
tact the originator
device's manufacturer.)
Confirm that the origi-
nator supports Class 1.
If the tag data link is
stopped or started, this
error may occur
according to the tim-
ing, but the system will
recover automatically.
This is not an error
because the connec-
tion is already closed.