Omron NY532-5400 User Manual page 414

Ny-series ipc machine controller industrial panel pc / industrial box pc
Hide thumbs Also See for NY532-5400:
Table of Contents

Advertisement

Appendices
Transferring the Connection Settings Data
Precautions for Correct Use
Precautions for Correct Use
• If the node addresses (IP addresses) are not set correctly, you may connect to the wrong Con-
troller and set incorrect device parameters. Download data only after you confirm that you are
connected to the correct Controller.
• If incorrect connection settings are set, it may cause equipment to operate unpredictably. Even
when the correct connection settings are set, make sure that there will be no effect on equip-
ment before you transfer the data.
• A connection error will result if the network variables that are used in the tag settings are not
set in the Controller. Before downloading the connection settings, check to confirm that the
network variables used in the tag settings are set in the Controller.
• If a communications error occurs, the output status depends on the specifications of the
device being used. When a communications error occurs for a device that is used along with
output devices, check the operating specifications and implement safety countermeasures.
• The built-in EtherNet/IP port is automatically restarted after the parameters are downloaded.
This restart is required to enable the tag set and connection information. Before you download
the parameters, check to confirm that problems will not occur with the equipment when the
port is restarted.
• Do not disconnect the Ethernet cable during the parameter download.
• The EtherNet/IP connections between relevant nodes is stopped during a download. Before
you download data in RUN mode, make sure that it will not affect the controlled system.
Also implement interlocks on data processing in ladder programming that uses EtherNet/IP
connections when the connections are stopped or a connection error occurs.
• In the EtherNet/IP network, if the device bandwidth usage (PPS) exceeds the unit's allowable
bandwidth (PPS), the EtherNet/IP connection operations may not agree with the settings.
If you increase the RPI value in such a case, there are cases when the problem can be
resolved (i.e., the operations agree the settings).
A-28
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User's Manual (W563)