Variable name
Meaning
_EIP_IPRTblErr
IP Route Table Error
_EIP_IdentityErr
Identity Error
_EIP_TDLinkCfgErr
Tag Data Link Setting
Error
_EIP_TDLinkOpnErr
Tag Data Link Con-
nection Failed
_EIP_TDLinkErr
Tag Data Link Com-
munications Error
_EIP_TagAdrErr
Tag Name Resolution
Error
_EIP_MultiSwONErr
Multiple Switches ON
Error
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User's Manual (W563)
3 System-defined Variables Related to the Built-in EtherNet/IP Port
Function
NY-series Controller: Indicates that the
default gateway settings or IP router table
settings are incorrect.
Or, a read operation failed.
TRUE: Setting incorrect or read failed
FALSE: Normal
NY-series Controller: Indicates that the
identity information for CIP communica-
tions 1 (which you cannot overwrite) is
incorrect. Or, a read operation failed.
TRUE: Setting incorrect or read failed
FALSE: Normal
NY-series Controller: Indicates that the tag
data link settings for CIP communications
1 are incorrect. Or, a read operation failed.
TRUE: Setting incorrect or read failed
FALSE: Normal
NY-series Controller: Indicates that estab-
lishing a tag data link connection for CIP
communications 1 failed.
TRUE: Establishing a tag data link con-
nection failed due to one of the
following causes.
• The information registered for
a target node in the tag data
link parameters is different
from the actual node informa-
tion.
• There was no response from
the remote node.
FALSE: Other than the above.
NY-series Controller: Indicates that a time-
out occurred in a tag data link connection
for CIP communications 1.
TRUE: A timeout occurred.
FALSE: Other than the above.
NY-series Controller: Indicates that tag
resolution for CIP communications 1 failed
(i.e., the address could not be identified
from the tag name).
TRUE: Tag resolution failed (i.e., the
address could not be identified
from the tag name). The follow-
ing causes are possible.
• The size of the network vari-
able is different from the tag
settings.
• The I/O direction that is set in
the tag data link settings does
not agree with the I/O direc-
tion of the variable in the Con-
troller.
• There is no network variable
in the Controller that corre-
sponds to the tag setting.
FALSE: Other than the above.
NY-series Controller: Indicates that more
than one switch turned ON at the same
time in CIP communications 1.
TRUE: More than one data link start/stop
switch changed to TRUE at the
same time.
FALSE: Other than the above.
Range of
Data type
values
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
Reference
page 3-18
page 3-19
page 3-19
3
page 3-19
page 3-19
page 3-20
page 3-20
3-7