 DNS
Setting
DNS
Priority DNS server
Secondary DNS server
*1
Domain name
*1 These settings are required when DNS is used.
 Host Name - IP Address
Setting
Host Name
IP Address
 Keep Alive
Setting
Keep Alive
Keep Alive Monitoring
Time
Linger option
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User's Manual (W563)
5 Sysmac Studio Settings for the Built-in EtherNet/IP Port
Enable using DNS if a DNS is used to resolve host names
when host names are specified for the remote communica-
tions nodes in CIP communications and socket instructions.
A DNS server is required to use DNS.
*1
Set the IP address of the DNS server. You can set priority
and secondary IP addresses.
Sets the domain name of the domain to which the built-in
EtherNet/IP port belongs. (Single-byte alphanumeric char-
acters, dots, and hyphens: 48 characters max.)
Addresses are converted according to this setting when
host names are used to specify remote communications
nodes.
They can be set even if DNS is not used. You can set up to
six host names. (You can use up to 200 single-byte alpha-
numeric characters, dots, and hyphens with up to 63 single-
byte alphanumeric characters between dots.)
Set the IP addresses of the registered hosts.
Set whether to use the remote node keep alive function of
connected servers and clients (such as socket services,
FTP server, Sysmac Studio, and TCP). If the keep-alive
function is used and the remote node does not respond
during the set keep-alive monitoring time, the connection is
disconnected. The connection is left open if the power sup-
ply to the remote node is turned OFF without warning. Use
the keep-alive function whenever possible.
• Use.
• Do not use.
The connection is disconnected if the keep-alive function is
used and the remote node does not respond during the
monitoring time set in the Keep Alive Monitoring Setting.
Setting range: 1 to 65,535 (seconds)
Set whether to specify the Linger Option for connections to
TCP or socket services. If the Linger Option is specified,
the port number is immediately opened even before the
port number is released after the socket closes (approx. 1
minute).
• Specify.
• Do not specify.
Description
Description
Description
Default
Do not use.
None
None
None
Default
None
None
Default
Use.
300
Do not specify.
5-3