Omron NY532-5400 User Manual page 104

Ny-series ipc machine controller industrial panel pc / industrial box pc
Hide thumbs Also See for NY532-5400:
Table of Contents

Advertisement

5 Sysmac Studio Settings for the Built-in EtherNet/IP Port
 Default Gateway
Setting
Default gateway
*1 Even if you select Fixed setting for both EtherNet/IP port and internal port, you can only set the default gate-
way for one of the ports.
 IP Router Table
Parameter
Destination IP address
Destination mask IP
address
Gateway address
Additional Information
IP Router Table Setting Example
To enable the Controller in an NY-series Industrial PC to perform Ethernet communications with
node B to send a CIP message etc. through an IP router, set the IP router table of the Controller
as follows.
When you set the IP router table, Controller sends packets to the gateway IP address
(130.25.36.253) if communications instructions are executed on Controller and addressed to
node B.
Windows
The host fields are set to 0 in the destination IP address.
On the other hand, for Windows in an NY-series Industrial PC to perform Ethernet communica-
tions with node B to send a CIP message etc. through the Controller in an NY-series Industrial
PC and an IP router, you need to set the default gateway and other settings for IP routing in Win-
dows, in addition to the IP router table of the Controller.
5-4
Set the IP address of the default gateway for the built-in
EtherNet/IP port. This setting is not required when the
default gateway is not used.
Set these settings when the built-in EtherNet/IP port is used
for tag data links or CIP message communications with
nodes on other IP network segments via an IP router. Set
them also to use the IP routing function of the built-in Ether-
Net/IP port as an IP router.
You can set up to 128 combinations of IP addresses and
gateway addresses.
Specify 0 for the host portions of the IP addresses.
NY-series Industrial PC
Built-in
Internal port
Internal port
EtherNet/IP port
Controller
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User's Manual (W563)
Description
*1
Description
130. 25. XX. XX
130.26.2.254
130.25.36.253
IP router or NX-series Controller
Default
None
Default
None
None
130. 26. XX. XX
Node B

Advertisement

Table of Contents
loading

Table of Contents