14 Checking Communications Status of Network and Troubleshooting
Connection status
General
Additional
Status
Status
(hex)
(hex)
08
---
Error code returned from target:
There is no Forward Open or Large
Forward Open service in the target
device.
D0
0001
Error code generated by originator:
The connection operation is
stopped.
D0
0002
Error code generated by originator:
The connection is being opened
(opening processing in progress).
OMRON error code
01
0810
Error code returned from target:
New data could not be obtained from
the Controller when opening con-
nection. (The Unit will automatically
recover, and attempt to open the
connection again.)
01
0811
Error code generated by originator:
New data could not be obtained from
the Controller when opening con-
nection. (The Unit will automatically
recover, and attempt to open the
connection again.)
14-12
Source of error
Configuration 1
This error does not
occur.
The connection was
stopped because the
Tag Data Link Stop
Bit was turned ON,
or the settings data
is being downloaded.
Either turn ON the
Tag Data Link Start
Switch, or wait until
the settings data has
been downloaded.
This code includes
fatal Controller errors
and Unit failure. To
handle these errors,
refer to the.NY-
series Troubleshoot-
ing Manual (Cat. No.
W564).
Wait until the open-
ing processing is
completed.
This error may occur
if the Controller's
task period was long
when opening the
connection or some
problem in the Con-
troller caused the
Controller to stop. If
the task period was
too long, operation
recovers automati-
cally. If the Controller
has stopped, iden-
tify the error from the
error information in
the Controller.
This error may occur
if the Controller's
task period was long
when opening the
connection. If the
task period was too
long, operation
recovers automati-
cally.
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User's Manual (W563)
Handling
Configuration 2
Configuration 3
Depends on the tar-
Depends on the origi-
get's specifications.
nator's specifications.
(Contact the target
(Contact the originator
device's manufacturer.)
device's manufacturer.)
The meaning of this
Depends on the origi-
error code is defined by
nator's specifications.
each vendor, so it
(Contact the originator
depends on the target's
device's manufacturer.)
specifications. (Con-
tact the target device's
manufacturer.)
The meaning of this
Depends on the origi-
error code is defined by
nator's specifications.
each vendor, so it
(Contact the originator
depends on the target's
device's manufacturer.)
specifications. (Con-
tact the target device's
manufacturer.)
The meaning of this
The meaning of this
error code is defined by
error code is defined by
each vendor, so it
each vendor, so it
depends on the target's
depends on the origina-
specifications. (Con-
tor's specifications.
tact the target device's
(Contact the originator
manufacturer.)
device's manufacturer.)
The meaning of this
The meaning of this
error code is defined by
error code is defined by
each vendor, so it
each vendor, so it
depends on the target's
depends on the origina-
specifications. (Con-
tor's specifications.
tact the target device's
(Contact the originator
manufacturer.)
device's manufacturer.)

Advertisement

Table of Contents
loading

Table of Contents