7 Tag Data Link Functions
Additional Information
You can also execute the Reset service of the Identity object for the Controller to clear the tag
data link settings. The procedures to execute the service from the Network Configurator is given
below.
(1) Connect the Network Configurator to the network.
(2) Select Tool - Setup Parameters on the main window.
Then the dialog box for the general parameter settings are displayed.
(3) Specify the target device and message to send.
• Target Node Address: Enter the IP address of the target device.
• Service:
• Class:
• Instance:
• Attribute:
• Data:
(4) Click the Send Button.

7-2-14 Saving the Network Configuration File

You can save device parameters set in the Network Configurator or device parameters uploaded from
the network in a network configuration file.
1
Select File - Save As.
The following dialog box is displayed.
Untitled.nvf is displayed as the default file name.
7-66
Select Reset.
Enter 01.
Enter 01.
Enter 00.
Enter 02.
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User's Manual (W563)