1-3

Built-in EtherNet/IP Port

1-3-1

Specifications

Communications protocol
Supported services
Number of ports
Physical layer
Transmission

specifications

CIP service: Tag
data links (cyclic
communications)
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User's Manual (W563)
Item
TCP/IP or UDP/IP
Sysmac Studio connection, tag data link, CIP message communi-
cations, socket services, FTP server, FTP client, SNMP agent,
DNS client, and BOOTP client
1 (With IP routing function)
100Base-TX, 10Base-T or 1000Base-T (1000Base-T or 100Base-
TX is recommended.)
Media access
CSMA/CD
method
Modulation
Baseband
Transmission
Star form
paths
Baud rate
1,000 Mbps (1000Base-T)
Transmission
Shielded twisted-pair (STP) cable, Category 5, 5e, or higher
media
Transmission dis-
100 m max. (distance between hub and node)
tance
Number of cascade
There is no limitation when an Ethernet switch is used.
connections
Number of connec-
128
tions
1 to 10,000 ms in 1-ms increments
Packet interval
Packet intervals can be set independently for each connection.
(refresh cycle)
(Data is refreshed over the network at the preset interval and does
not depend on the number of nodes.)
Allowed communi-
20,000 pps
cations bandwidth
Note The heartbeat is included.
per Unit
Number of regis-
256
trable tags
Network variables
Tag types
CIO, Work, Holding, DM, and EM Areas cannot be used.
Specifications
NY52-
Unit version 1.12 or later