Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 328

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

DXOR(P) [when three operands are set]
RnPCPU
RnCPU RnENCPU
(Process)
These instructions perform an XOR operation on the two sets of 32-bit binary data specified.
Ladder
(s1)
FBD/LD
EN
ENO
s1
d
s2
■Execution condition
Instruction
DXOR
DXORP
Setting data
■Description, range, data type
Operand
Description
(s1)
Exclusive OR data or the start device where exclusive OR
data is stored
(s2)
Exclusive OR data or the start device where exclusive OR
data is stored
(d)
Start device for storing the operation result
EN
Execution condition
ENO
Execution result
• In safety programs executed by the Safety CPU, only safety devices and safety labels of data types described in the table
can be used.
■Applicable devices
Operand
Bit
X, Y, M, L,
SM, F, B, SB,
FX, FY
(s1)
(s2)
(d)
• In safety programs executed by the Safety CPU, only the following safety devices and constants can be used.
Operand
Bit
SA\X, SA\Y, SA\M, SA\SM, SA\B
(s1)
(s2)
(d)
6 BASIC INSTRUCTIONS
326
6.3 Logical Operation Instructions
RnPCPU
RnSFCPU RnSFCPU
(Redundant)
(Standard)
(Safety)
(s2)
(d)
Execution condition
Word
J\
T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
ST
ENO:=DXOR(EN,s1,s2,d);
ENO:=DXORP(EN,s1,s2,d);
Range
-2147483648 to 2147483647
-2147483648 to 2147483647
Double word Indirect
U\G, J\,
Z
LT, LST,
U3E\(H)G
LC
Word
SA\T, SA\ST, SA\C, SA\D, SA\W, SA\SD
Data type
Data type (label)
32-bit signed binary
ANY32
32-bit signed binary
ANY32
32-bit signed binary
ANY32
Bit
BOOL
Bit
BOOL
Constant
specification
LZ
K, H E
Constant
K, H
Others
$

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents