Processing details
• These instructions turn on the bit, corresponding to the binary value specified by the lower (n) bits in the device specified by
(s), in the device specified by (d)
n=3
(s)
=6
1 1 0
(d)
• Specify a value 1 to 8 for (n).
• When (n)=0, no processing is performed and the values in the device specified by (d) remain unchanged.
• A bit device is treated as 1 bit, and a word device is treated as 16 bits.
Operation error
Error code
Description
(SD0)
3401H
The value specified by (n) is out of the range, 0 to 8.
6 BASIC INSTRUCTIONS
472
6.6 Data Conversion Instructions
7
6 5 4 3 2 1 0
0 1
0 0 0 0 0 0
ON