Converting 32-Bit Unsigned Binary Data To 16-Bit Unsigned Binary Data - Mitsubishi Electric MELSEC iQ-R Series Programming Manual

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Converting 32-bit unsigned binary data to 16-bit unsigned binary
data
UDINT2UINT(P)
RnPCPU
RnCPU RnENCPU
(Process)
These instructions convert the specified 32-bit unsigned binary data to 16-bit unsigned binary data.
Ladder
(s)
FBD/LD
EN
ENO
s
d
*1 The engineering tool with version "1.035M" or later supports the ST.
■Execution condition
Instruction
UDINT2UINT
UDINT2UINTP
Setting data
■Description, range, data type
Operand
Description
(s)
Binary data or the start device where the binary data is
stored
(d)
Device for storing the converted binary data
EN
Execution condition
ENO
Execution result
■Applicable devices
Operand
Bit
X, Y, M, L,
SM, F, B, SB,
FX, FY
(s)
(d)
6 BASIC INSTRUCTIONS
422
6.6 Data Conversion Instructions
RnPCPU
RnSFCPU RnSFCPU
(Redundant)
(Standard)
(Safety)
(d)
Execution condition
Word
J\
T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
*1
ST
ENO:=UDINT2UINT(EN,s,d);
ENO:=UDINT2UINTP(EN,s,d);
Range
0 to 4294967295
Double word Indirect
U\G, J\,
Z
LT, LST,
U3E\(H)G
LC
Data type
Data type (label)
32-bit unsigned binary
ANY32_U
16-bit unsigned binary
ANY16_U
Bit
BOOL
Bit
BOOL
Constant
specification
LZ
K, H E
Others
$

Hide quick links: