Technical data of the CU240E
CU240E
Feature
Operating voltage
Heat loss
Setpoint resolution
Digital inputs
(dependent on the CU
type)
Analog inputs
Digital outputs
Analog outputs
Weight
224
Data
Supply from the Power Module
< 40W
0.01 Hz
6, floating; PNP/NPN switchable
Low < 5 V, High > 10 V, maximum input voltage 30 V, 5.5 mA
2, with 10-bit resolution
AI0: 0 V to 10 V, 0 mA to 20 mA and -10 V to+10 V
AI1: 0 V to 10 V and 0 mA to 20 mA
Both analog inputs can also be configured as digital inputs
3 relay outputs, 30 V DC / max. 0.5 A for a resistive load
2
AO0: 0 V to 10 V or 0 mA to 20 mA
AO1: 0 mA to 20 mA
0.21 kg