Oil pressure switch-min
In all types of oil train, the minimum oil pressure is expected from phase 38. If no oil
pressure is detected when the maximum time (parameter 217) has elapsed or if,
subsequently, the oil pressure drops, the system initiates lockout.
No.
Parameter
Max. Waiting time for detection of detector or pressure signal (e.g. homerun,
217
preignition «Lo»)
Error
Diagnostic
code
code
20
0
20
1
During the safety times (TSA1/TSA2), the signal from pressure switch-min is only
assessed after a certain period of time in order to ignore the pressure shocks that occur
the moment the valves open. The time to elapse for signal assessment can be
parameterized.
No.
Parameter
269
Oil: Time to respond to pressure faults within safety time 1 (TSA1) and safety
time 2 (TSA2)
369
Fuel 1 oil: Time to respond to pressure faults within safety time 1 (TSA1) and
safety time 2 (TSA2)

7.3.8 Setting the time for checking the pressure switch

For oil pressure switch-min, the point in time from which the check is made can be
set via parameter 276 (active from phase 38, or from safety time
No.
Parameter
276
Oil: Pressure switch-min input
0 = inactive
1 = active from phase 38
2 = active from safety time (TSA)
376
Fuel 1 Oil: Pressure switch-min input
0 = inactive
1 = active from phase 38
2 = active from safety time (TSA)
Basic documentation LMV36...
7 Basic unit
Meaning for the LMV36... system
Pressure switch-min (Pmin)
No min. oil pressure
Gas shortage start prevention
(TSA)
).
CC1P7544en