Assigning the room and group
Figure 170: ROOM - GROUP settings level
– Start point: ROOM - GROUP settings level
1.
Select ROOM.
= ROOM illuminates.
2.
Run your finger along the touchring until the desired number appears.
3.
Select GROUP.
= GROUP illuminates.
4.
Run your finger along the touchring until the desired number appears.
5.
Select SAVE to save the settings.
= The message SAVED briefly appears.
= Room and group have been assigned and saved.
= START SCENE settings level appears.
Notes
• Settings are only saved if SAVE is selected.
• Selecting SAVE automatically saves all values displayed on the touchscreen.
• To switch to the WAITING TIME settings level directly (without saving), select NEXT STEP.
Parameter
ROOM
GROUP
Table 68: ROOM - GROUP setting options
Assigning a waiting time
Figure 171: START SCENE settings level
– Start point: START SCENE settings level
1.
Select NEXT STEP.
= WAITING TIME settings level appears.
LM-CIRIA operating and commissioning manual 2.0 | 06. 2012 | en
Commissioning the field level
Value range
1 – 99
0 – 99
109