Defining the stop process
Figure 162: STOP PROCESS settings level
– Start point: STOP PROCESS settings level
1.
Select NUMBER.
= NUMBER illuminates.
2.
Run your finger along the touchring until the desired setting appears.
3.
Select SAVE to save the setting.
= The message SAVED briefly appears.
= Setting is saved.
= DAY - LOOPS settings level appears.
Notes
• Settings are only saved if SAVE is selected.
• Selecting SAVE automatically saves all values displayed on the touchscreen.
• To switch to the START SCENE settings level directly (without saving), select NEXT STEP.
NUMBER parameter
1
2
3
Table 60: NUMBER setting options
Setting day(s) and number of loops
Figure 163: DAY - LOOPS settings level
– Start point: DAY - LOOPS settings level
1.
Select WHEN.
= WHEN illuminates.
2.
Run your finger along the touchring until the desired setting appears.
3.
Select LOOPS.
= LOOPS illuminates.
LM-CIRIA operating and commissioning manual 2.0 | 06. 2012 | en
If the start scene is recalled manually, the scene sequence will
stop at the stop time.
If the scene sequence begins at the start time, the sequence
will stop at the stop time.
The scene sequence will stop at the stop time.
Commissioning the field level