Assigning group and building service type
Figure 156: GROUP - TYPE settings level
– Start point: GROUP - TYPE settings level
1.
Select GROUP.
= GROUP illuminates.
2.
Run your finger along the touchring until the desired group address appears.
3.
Select TYPE.
= TYPE illuminates.
4.
Run your finger along the touchring until the desired number appears.
5.
Select SAVE to save the settings.
= The message SAVED briefly appears.
= Group and building service type are assigned and saved.
= SWITCH ENTRY selection level appears.
Notes
• Settings are only saved if SAVE is selected.
• Selecting SAVE automatically saves all values displayed on the touchscreen.
Parameter
GROUP
Table 56: GROUP setting options
Building service type
COMMON (all building services)
Brightness
Blind position
Slat angle
Screen
Colour temperature
Window
Curtain
Temperature
Air exchange
Table 57: Selection of TYPE setting options
LM-CIRIA operating and commissioning manual 2.0 | 06. 2012 | en
Available group address in the room to which the LM-CIRIA
control unit is assigned
Building service type number
1
2
3
4
10
13
65
64
11
39