Section 10
Control
10.3.9.3
256
OPENPOS
CLOSEPOS
EXE_OP
EXE_OP
tStartMove timer
IEC05000099 V1 EN
Figure 123:
Open command with open position indication
Error handling
Depending on the error that occurs during the command sequence the error signal will
be set with a value. Table
these specified in IEC 61850-8-1 standard. The list of values of the "cause" are in
order of priority. The values are available over the IEC 61850. An output L_CAUSE
on the function block indicates the latest value of the error during the command.
Table 196:
Vendor specific cause values for Apparatus control in priority order
Apparatus control
Description
function
–22
wrongCTLModel
–23
blockedForCommand
–24
blocked-for-open-command
–25
blocked-for-close-command
–30
longOperationTime
–31
switch-not-start-moving
–32
persistent-intermediate-state
–33
switch-returned-to-initial-position
–34
switch-in-bad-state
–35
not-expected-final-position

Circuit switch SXSWI

The users of the Circuit switch (SXSWI) is other functions such as for example, switch
controller, protection functions, autorecloser function, or a 61850 client residing in
another IED or the operator place. SXSWI executes commands, evaluates block
conditions and evaluates different time supervision conditions. Only if all conditions
tOpenPulse
tOpenPulse
196
describes vendor specific cause values in addition to
1MRK 511 287-UEN A
AdaptivePulse=FALSE
AdaptivePulse=TRUE
en05000099.vsd
Technical manual