Function Block; Signals; Settings - ABB REC650 Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

Section 7
Voltage protection
7.4.3
7.4.4
7.4.5
Table 131:
LOVPTUV Group settings (basic)
Name
Operation
UPE
tTrip
Table 132:
LOVPTUV Group settings (advanced)
Name
tPulse
tBlock
tRestore
176

Function block

LOVPTUV
U3P*
BLOCK
CBOPEN
BLKU
IEC09000279_1_en.vsd
IEC09000279 V1 EN
Figure 76:
LOVPTUV function block

Signals

Table 129:
LOVPTUV Input signals
Name
U3P
BLOCK
CBOPEN
BLKU
Table 130:
LOVPTUV Output signals
Name
TRIP
START

Settings

Values (Range)
Unit
Off
-
On
1 - 100
%UB
0.000 - 60.000
s
Values (Range)
Unit
0.050 - 60.000
s
0.000 - 60.000
s
0.000 - 60.000
s
TRIP
START
Type
Default
Description
GROUP
-
Three phase group signal for voltage inputs
SIGNAL
BOOLEAN
0
Block of function
BOOLEAN
0
Circuit breaker open
BOOLEAN
0
Block from voltage circuit supervision
Type
Description
BOOLEAN
Trip signal
BOOLEAN
Start signal
Step
Default
-
Off
1
70
0.001
7.000
Step
Default
0.001
0.150
0.001
5.000
0.001
3.000
1MRK 511 287-UEN A
Description
Operation Off/On
Operate voltage in% of base voltage
Ubase
Operate time delay
Description
Duration of TRIP pulse
Time delay to block when all 3ph voltages
are not low
Time delay for enable the function after
restoration
Technical manual